Virtual Switches

43 - Virtual Selector Switches

BE1-851 relays have four virtual selector switches that can provide manual control, locally and remotely,

without using physical switches and/or interposing relays. Only two virtual selector switches are provided

when style option 1 is V or W. Each virtual switch can be set for one of three modes of operation to

emulate virtually any type of binary (two position) switch. An example would be an application that

requires a recloser or 51N ground cutoff. The traditional approach might be to install a switch on the panel

and wire the output to a contact sensing input on the relay. Instead, a virtual switch can be used to reduce

costs with the added benefit of being able to operate the switch both locally through the HMI and remotely

from a substation computer or through a modem connection to a remote operator’s console.
The state of the switches can be controlled from the HMI or ASCII command interface. The BESTlogic

mode setting can set control actions. When set for the On/Off/Pulse mode, each switch can be controlled

to open (logic 0), close (logic 1), or pulse such that the output toggles from its current state to the opposite

state and then returns. Additional modes allow the switch operation to be restricted. In the On/Off mode,

the switch emulates a two-position selector switch, and only open and close commands are accepted. In

the Off/Momentary On mode, a momentary close, spring return switch is emulated and only the pulse

command is accepted. Because switch status information is saved in nonvolatile memory, the relay

powers up with the switches in the same state as when the relay was powered down.
Each virtual selector switch function block (see Figure 4-39) has one output: 43, 143, 243, or 343. The

output is TRUE when the switch is in the closed state; the output is FALSE when the switch is in the open

state. Since both the output and the inverse of the output of these switches can be used as many times

as desired in your programmable logic, they can emulate a switch with as many normally open and

normally closed decks as desired.

Figure 4-39. Virtual Selector Switches Logic Block

User specified labels could be assigned to each virtual switch and to both states of each switch. In the

previous differential cutoff switch example, you might enable one of the switches in BESTlogic as On/Off

and connect the output of that switch to the Block input of the 51P protection element block. This would

disable the differential when the switch is closed (logic 1) and enable it when the switch is open (logic 0).

For the application, you might set the switch label to be 51_CUTOFF (10 character maximum). The

closed position on the switch might be labeled DISABLD (7 character maximum) and the open position

might be labeled NORMAL. Section 7, BESTlogic Programmable Logic, has more details about setting

user programmable names for programmable logic variables.

BESTlogic™ Settings for Virtual Selector Switches

BESTlogic settings are made from the BESTlogic Function Element screen in BESTCOMS. Figure 4-40

illustrates the BESTCOMS screen used to select BESTlogic setting for the Virtual Switch element. To

open the BESTlogic Function Element screen for Virtual Switch, select Virtual Switches from the Screens

pull-down menu. Then select the BESTlogic button for the 43, 143, 243, or 343 element. Alternately,

settings may be made using SL-<x>43 ASCII command.

4-36

BE1-851 Protection and Control