Table 8-23. BUS Virtual Switch Logic

Switch

Purpose

Mode

Label

State Labels

True

False

43

N/A

0 (Disable)

SWITCH_43

CLOSED

OPEN

143

N/A

0 (Disable) SWITCH_143

CLOSED

OPEN

243

N/A

0 (Disable) SWITCH_243

CLOSED

OPEN

343

Put the relay in test mode so

that reclosing and breaker

failure are disabled when virtual

switch is closed.

2 (On/Off) TESTENABLE

TSTMODE

NORMAL

101

Virtual Control Switch to trip bus

breaker.

1 (Enable)

N/A

N/A

N/A

Table 8-24. BUS Virtual Outputs

Output

Purpose

Description

Label

State Labels

True

False

VOA

(OUTA)

Alarm Output Contact.

Change state of alarm contact

when relay failure or major

programmable alarm is TRUE.

(Style Dependent.)

ALARM

ACTIVE NORMAL

BESTlogic Expression: VOA=ALMMAJ

VO1

(OUT1)

Bus breaker trip.

Trip breaker for virtual control

switch trip OR for 51 trip when in

normal mode. Trip bus breaker

for 41 trip after coordination time

delay when in feeder backup

mode. Close OUT1 for any trip

when in test mode.

BKR_TRIP

TRIP

NORMAL

BESTlogic Expression: VO1=101T+VO8*/SG0+62*SG1+VO11*VO15

VO2

(OUT2)

Bus breaker close.

Close breaker when virtual

breaker control switch is

operated to close.

BKR_CLOSE

CLOSE NORMAL

BESTlogic Expression: VO2=101C

VO3

(OUT3)

N/A

N/A

VO3

TRUE

FALSE

BESTlogic Expression: VO3=/IN2

VO4

(OUT4)

Bus fault trip (86B).

Trip bus breaker via lockout for

bus faults (50T with 2-4 cycles

delay) when in normal mode and

not in test mode.

BUS_TRIP

TRIP

NORMAL

BESTlogic Expression: VO4=VO9*SG0*/VO15

8-48

BE1-851 Application

9289900990 Rev R