Operating settings for reclosing, Operating settings for reclosing -31, Figure 4-34. reclosing screen -31 – Basler Electric BE1-851 User Manual

Page 87: Table 4-15. bestlogic settings for reclosing -31

Advertising
background image

used. Then, select the BESTlogic variable, or series of variables to be connected to the input. Select

Save when finished to return to the BESTlogic Function Element screen. For more details on the

BESTlogic Expression Builder, see Section 7, BESTlogic Programmable Logic. Select Done after the

settings have been completely edited.
Table 4-15 summarizes the BESTlogic settings for Reclosing.

Table 4-15. BESTlogic Settings for Reclosing

Function

Range/Purpose

Default

Mode

0 = Reclosing disabled
1 = Standard power-up operation. After power-up, the STATUS logic must

be TRUE for the Reset time delay or the recloser automatically goes

to Lockout. If the STATUS logic stays TRUE for reset time delay, the

recloser goes to Reset.

2 = Power-up to close. If the recloser was in the Reset state when power

was lost and when power is restored the STATUS logic is FALSE

(breaker open) and the RI logic is TRUE, the recloser will initiate the

first reclose operation. If the STATUS logic stays TRUE for the reset

time delay, the recloser goes to Reset.

0

RI

OR logic term to initiate the operation of the reclosing function.

0

STATUS

OR logic term to indicate breaker status.
TRUE/1 = closed, FALSE/0 = open.

0

WAIT

OR logic term to momentarily disable but not reset the recloser.

0

BLK/DTL OR logic term to disable the recloser (drive to lockout).

0

Operating Settings for Reclosing

Operating settings are made using BESTCOMS. Figure 4-34 illustrates the BESTCOMS screen used to

select operational settings for the reclosing element. To open the screen, select Reclosing from the

Screens pull-down menu. Alternately, settings may be made using the S<g>-79 ASCII command.
Settings can also be made from the front panel HMI using Screens 5.x.4.1 through 5.x.4.5 where x equals

1 for Setting Group 0, 2 for Setting Group 1, 3 for Setting Group 2, and 4 for Setting Group 3.

Figure 4-34. Reclosing Screen

9289900990 Rev R

BE1-851 Protection and Control

4-31