HMI Display

This tab (see Figure 14-8) allows the user to change the screen scroll list. Only the code for the latest

version of BESTCOMS is contained within BESTCOMS. If you have an earlier version of the embedded

firmware in your relay and selected that information on the General Information tab under General

Operation Screen, you can select a screen scroll item in BESTCOMS that is not available in the relay. If

you do, you will get an error code immediately.

Figure 14-8. General Operation Screen, HMI Display Tab

Setting Group Selection

Pull down the Screens menu and select Setting Group Selection or click on the Setting Group

Selection icon that is shown at the right margin of this paragraph. This screen (Figure 14-9)

does not have folder tabs and it is labeled Setting Group Selection/Setting Group Automatic

Control Settings.
Setting group selection involves programming the relay to automatically select one group out of four

protective element setting groups in response to system conditions. When the system is normal, the

default or normal group is 0. Auxiliary setting groups allow adapting the coordination settings to optimize

them for a predictable situation. Sensitivity and time coordination settings can be adjusted to optimize

sensitivity or clearing time based upon source conditions or to improve security during overload

conditions. Near the bottom of Figure 14-9, there is a Monitor Setting window for Setting Groups 1, 2 and

3. This field in each group allows you to select which element controls that specific group selection. The

Switch Threshold sets the level for the monitored element and the Switch Time sets the time delay to

prevent the group change from changing the instant that the monitored element exceeds the Switch

Threshold setting. Return Threshold and Time does the same thing for changing back to the previous

group.
You do not have to depend only on monitored conditions to change group selection. The active Setting

Group can be controlled at any point in time by the setting group control logic. (Refer to Section 4,

Protection and Control, for more information on Setting Groups.) The setting group control also has an

alarm output variable SGC (Setting Group Changed). This output is asserted whenever the BE1-851

switches from one setting group to another. The alarm bit is asserted for the SCCON time setting.
You can click in the Setting Group Change (SGC) Alarm Timer (Sec) field and set the SGCON Time

setting.