Table 13-24. Command Settings

Style Number

Commands

Phase

Neutral

x1xxxxx

S0-51P=0.1A,5.0,I2

S0-51N=0.1A,5.0,I2

x3xxxxx

S0-51P=0.5A,5.0,I2

S0-51N=0.1A,5.0,I2

x5xxxxx

S0-51P=0.5A,5.0,I2

S0-51N=0.5A,5.0,I2

Step 5:

Apply the appropriate current value to the Phase A current input and measure the time

between the application of current and OUT1 closing. Verify that the timing is within the

acceptance range stated in Table 13-25.

Table 13-25. Timing Ranges

Style Number

Current

Low Limit

High Limit

x1xxxxx

0.2 amps

4.205 sec

4.647 sec

x1xxxxx

1.0 amps

1.272 sec

1.405 sec

x1xxxxx

2.6 amps

0.935 sec

1.033 sec

x1xxxxx

4.0 amps

0.846 sec

0.934 sec

x3xxxxx or x5xxxxx

1.0 amps

4.205 sec

4.647 sec

x3xxxxx or x5xxxxx

5.0 amps

1.272 sec

1.405 sec

x3xxxxx or x5xxxxx

13.0 amps

0.935 sec

1.033 sec

x3xxxxx or x5xxxxx

20.0 amps

0.846 sec

0.934 sec

Step 6:

Transmit the appropriate command from Table 13-26 to reprogram the pickup, time delay

setting, and curve type.

Table 13-26. Command Settings

Style Number

Commands

Phase

Neutral

x1xxxxx

S0-51P=0.1A,9.9,I2

S0-51N=0.1A,9.9,I2

x3xxxxx

S0-51P=0.5A,9.9,I2

S0-51N=0.1A,9.9,I2

x5xxxxx

S0-51P=0.5A,9.9,I2

S0-51N=0.5A,9.9,I2


Step 7:

Apply the appropriate current value to the Phase A current input and measure the time

between the application of current and OUT1 closing. Verify that the timing is within the

acceptance range stated in Table 13-27.






9289900990 Rev R

BE1-851 Testing and Maintenance

13-11