Basler Electric BE1-851 User Manual

Page 62

Advertising
background image

At the top center of the screen is a pull-down menu labeled Logic. This menu allows viewing of the

BESTlogic settings for each preprogrammed logic scheme.
Using the pull-down menus and buttons, make the application-appropriate settings to the Setting Group

Control function. Table 4-3 summarizes the operating settings for Setting Group Control.

Table 4-3. Operating Settings for Setting Group Control.

Setting

Range

Increment

Unit of Measure

Default

Switch Threshold

0 – 150

1

% of SG0 51* Pickup

0

Switch Time

0 = Disabled, 1 – 60

1

Minutes

0

Return Threshold

0 – 150

1

% of SG0 51* Pickup

0

Return Time

0 = Disabled, 1 – 60

1

Minutes

0

Monitored Element

See Note

N/A

N/A

51P

Setting Group Change

(SGC) Alarm Timer

0 = Disabled, 1 - 10

1

Seconds

5

The SGC alarm output (SGC ACTIVE) is typically used to provide an external acknowledgement that a

setting group change occurred. If SCADA was used to change the active group, then this signal could be

monitored to verify that the operation occurred. The SGC ACTIVE alarm output ON time is user

programmable using the Setting Group Change (SGC) Alarm Timer (sec.) setting on the BESTCOMS

screen (refer to Figure 4-5). The setting should be set greater than the SCADA scan rate.

Example 1. Set the SGC alarm timer to 5 seconds. Refer to Figure 4-5.

Setting Group Change (SGC) Alarm timer (sec.):

5


Automatic control of the active setting group allows the relay to automatically change configuration for

optimum protection based on the current system conditions. For example, in locations where seasonal

variations can cause large variations in loading, the overcurrent protection can be set with sensitive

settings during the majority of the time and switch to a setting group with lower sensitivity (higher pickups)

during the few days of the year when the loading is at peak.
There are five settings for each group that are used for automatic control. Each group has a switch to

threshold and time delay, a return threshold and time delay, and a monitored element. The switch to and

return thresholds are a percentage of the SG0 pickup setting for the monitored element. The monitored

element can be any of the 51 protective functions. Thus, if you wish to switch settings based upon

loading, you could set it to monitor 51P. If you with to switch settings based upon unbalance, you could

set it to monitor 51N or 51Q. When the monitored element is 51P, any one phase must be above the

switch to threshold for the switch to time delay for the criteria to be met. All phases must be below the

return threshold for the return time delay for the return criteria to be met.
Figure 4-6 shows an example of using the automatic setting group selection settings to change setting

groups based upon loading. Figure 4-5 illustrates the operating settings used in the diagram shown in

Figure 4-6. Note that the AUTO input must be at a TRUE logic state in order to allow the automatic logic

to operate. At time = 0, current begins to increase. When current reaches 75 percent of pickup, setting

group two begins timing (30 minutes). When current reaches 90 percent of pickup, setting group three

begins timing (5 minutes). After 5 minutes, at time = 37, with the current still above setting group three

threshold, setting group three becomes active and the setting group change output pulses. At time = 55,

setting group two timer times out but no setting group change occurs because a higher setting group

takes precedence. The faint dashed line for SG2, between time = 55 and 75 shows that setting group two

would be active except for setting group three. Current decreases to 75 percent at time = 70 and setting

NOTE

Monitored element for sensing input type H is any 51 element: 51P, 51N, 51Q,

791, 792, 793, and 794. Monitored element for Sensing Input Type G is any 51

element: 51P, 51N, 151N, 791, 792, 793, and 794.

4-6

BE1-851 Protection and Control

9289900990 Rev R

Advertising