Basler Electric BE1-851 User Manual

Page 196

Advertising
background image

Output

Purpose

Description

Label

State Labels

True

False

VO5

(OUT5)

Breaker failure trip

contact.

Trip backup if breaker failure

protection times out.

BKR_FAIL

TRIP

NORMAL

BESTlogic Expression: VO5=BFT

VO6

N/A

N/A

VO6

TRUE

FALSE

BESTlogic Expression: VO6=0

VO7

N/A

N/A

VO7

TRUE

FALSE

BESTlogic Expression: VO7=0

VO8

Reclose initiate

expression.

Allow reclose when the

recloser is not disabled. To

operate, reclose must be

enabled by IN2 and Virtual

Switch 143 and virtual breaker

control switch slip contact.

RCL_INI

INI

NORMAL

BESTlogic Expression: VO8=IN2*/143*101SC

VO9

Recloser drive to lockout

expression.

Drive recloser to lockout to

disable it if the breaker fails.

RCL_DTL

DTL

NORMAL

BESTlogic Expression: VO9=VO5

VO10

Breaker failure initiate

expression.

Initiate breaker failure timing

when protective trip expression

is TRUE or when external

initiate contact is sensed and

any of the fault detectors is

picked up.

BFI

INI

NORMAL

BESTlogic Expression: VO10=VO11+IN3*150TPPU+IN3*150TNPU+IN3*150TQPU

VO11

Protective Trip

Expression.

TRUE when any 50, 150, or 51

element times out.

PROT_TRIP

TRIP

NORMAL

BESTlogic Expression: VO11=50TPT+50TNT+50TQT+150TPT+150TNT+150TQT+51PT+51NT+51QT

VO12

Protection Picked Up

Expression.

TRUE when any 50, 150, or 51

element picks up.

PROT_PU

PU

NORMAL

BESTlogic Expression:

VO12=50TPPU+50TNPU+50TQPU+150TPPU+150TNPU+150TQPU+51PPU+51NPU+51QPU

VO13

N/A

N/A

VO13

TRUE

FALSE

BESTlogic Expression: VO13=0

VO14

N/A

N/A

VO14

TRUE

FALSE

BESTlogic Expression: VO14=0

VO15

The relay is in test mode,

breaker failure is

disabled, and reclosing is

disabled.

TRUE if IN4 is de-energized or

if Virtual Switch 343 is closed.

TEST_MODE

TEST

NORMAL

BESTlogic Expression: VO15=/IN4+343





8-40

BE1-851 Application

9289900990 Rev R