At the top center of the BESTlogic Function Element screen is a pull-down menu labeled Logic. This

menu allows viewing of the BESTlogic settings for each preprogrammed logic scheme. User must be

selected on this menu to allow changes to the mode and inputs of the function/element.
Enable the setting group control function by selecting its mode of operation from the Mode pull-down

menu. To connect the setting group control functions inputs, select the button for the corresponding input

in the BESTlogic Function Element screen. The BESTlogic Expression Builder screen will open. Select

the expression type to be used. Then, select the BESTlogic variable or series of variables to be

connected to the input. Select Save when finished to return to the BESTlogic Function Element screen.

For more details on the BESTlogic Expression Builder, see Section 7, BESTlogic Programmable Logic.

Select Done once the settings have been completely edited.

Figure 4-2. BESTlogic Function Element Screen, Setting Group Selection


Table 4-1 summarizes the BESTlogic settings for Setting Group Control. These settings will determine

how the function selects the active setting group when manual logic selection is enabled.

Table 4-1. BESTlogic Settings for Setting Group Control

Function

Range/Purpose

Default

Mode

0 = Disabled, 1 = Discrete Inputs, 2 = Binary Inputs (If Auto mode is

desired, logic mode must be either 1 or 2.)

1 (Discrete Inputs)

D0

Logic expression. Meaning is dependent upon the Mode setting.

0

D1

Logic expression. Meaning is dependent upon the Mode setting.

0

D2

Logic expression. Meaning is dependent upon the Mode setting.

0

D3

Logic expression. Meaning is dependent upon the Mode setting.

0

Automatic Logic Expression. When TRUE enables automatic control and when

FALSE enables logic control.

0

Manual (logic) control reads the status of the logic inputs to the setting group control function block to

determine what setting group should be active. For the logic inputs to determine which setting group

should be active, the AUTOMATIC input must be logic 0. The function block logic mode setting

determines how it reads these logic inputs. There are three possible logic modes as shown in Table 4-1.

9289900990 Rev R

BE1-851 Protection and Control

4-3