101 - virtual breaker control switch, 101 - virtual breaker control switch -38, Figure 4-41. 101 function block -38 – Basler Electric BE1-851 User Manual

Page 94

Advertising
background image

CS/CO-x43 Command Examples:

Example 1. Read the current status of virtual switch 43.

>CO-43

0

Example 2. Momentarily toggle the state of switch 43 to closed.

>CS-43=P

43=P SELECTED

>CO-43=P

43=P EXECUTED

Example 3. An example of an operate command not matching the select command.

>CS-243=P

CS-243 SELECTED

>CO-243=1

ERROR:NO SELECT

Retrieving Virtual Selector Switches Status from the Relay

The state of each virtual selector switch can be determined from HMI Screen 1.5.4. This information is

also available through the ASCII command interface by using the RG-STAT or RG-x43STAT commands.

This is not available through BESTCOMS. See Section 6, Reporting and Alarms, General Status

Reporting, for more information.
HMI Screens 2.1.1 through 2.1.4 provide switch control and can also display the current status of their

respective switches. ASCII command CO-x43 returns the state of each virtual selector switch in a read-

only mode. See the previous example 1.

101 - Virtual Breaker Control Switch

The virtual breaker control switch (see Figure 4-41) provides manual control of a circuit breaker or switch

without using physical switches and/or interposing relays. Both local and remote control is possible. A

virtual switch can be used instead of a physical switch to reduce costs with the added benefit that the

virtual switch can be operated both locally from the HMI and remotely from a substation computer or

modem connection to an operator’s console.

Figure 4-41. 101 Function Block

The breaker control switch emulates a typical breaker control switch with a momentary close, spring

return, trip contact (Output 101T), a momentary close, spring return, close contact (Output 101C), and a

slip contact (Output 101SC). The slip contact output retains the status of the last control action. That is, it

is FALSE (open) in the after-trip state and TRUE (closed) in the after-close state. Figure 4-42 shows the

state of the 101SC logic output with respect to the state of the 101T and 101C Outputs.

4-38

BE1-851 Protection and Control

9289900990 Rev R