Basler Electric BE1-851 User Manual

Page 8

Advertising
background image

Application Firmware

Version and Date

Change

3.43.09, 03/03

Added the capability of changing Modbus Password Security with the

ASCII command.

Enhanced the 3

rd

parameter {C} for the SP-CURVE command (user

programmable time curve).

Insured year change update with IRIG connected, under all conditions.

3.43.07, 03/02

Enhanced fault data capture.

Improved operation of the front panel Reset key with resettable data.

Improved the accuracy of oscillographic waveform amplitude.

Enhanced SA-BKR mode; more than one setting can be entered.

Improved the display of the reclose cycle.

Improved settings change capability.

Automatically display the Target screen on the HMI after fault.

Added operation of the 43 switches on the HMI scroll list.

3.43.06, 02/02

2.43.06, 02/02

Improved accuracy of oscillographic waveform amplitude

measurement.

Added functionality of DNP Version 2 with BESTCOMS.

3.43.05, 02/02

2.43.05, 02/02

Improved modes of operation for SA-BKR command used to read or set

alarm settings.

Changed alarm functionality so that an alarm threshold value of zero

will disable the alarm.

Mode settings entered with multiple digits now return an error. Only one

digit may be entered for a mode setting.

Improved the BE1-851 to prevent “lockup” from issuing too many

settings changes at one time.

3.43.00, 02/00

Updated the GF-VER and RG-VER commands to report Model Number

BE1-851G for style type Gxxxxx and Model Number BE1-851 for style

type Hxxxxx.

Updated to support sensing type G (Florida Power Light) which

replaces 51Q with 151N, 50TQ with 250TN, and 150TQ with 350TN.

(This hex file version only works with style type Hxxxxx.)

3.42.01, 11/99

Added DNP 3.0, Level 2 compliance. Requires Version 3.xx hardware.

Added support for Version 3 hardware with additional memory.

Oscillographic recording is as follows:

Feature

Version 3.xx

Number of Oscillographic Records 16
Length of Oscillographic Records

15 cycles each

Sample Resolution

24 samples/cycle

Improved target reporting function.

The trip LED only latches when there are targets to be displayed on the

HMI. The “pickup” condition, indicated by the Trip LED flashing, is now

a higher priority than latching to indicate that targets are being

displayed on the HMI.

Improved HMI Target screen format. Screen now reports targets in a

text format. Additional information such as fault current magnitudes and

time and date of the fault were moved to a lower menu branch so that

the targets are all that is displayed unless the user wants more detail.

Added functionality to reset targets using a programmable logic

expression in addition to the HMI Reset key and the ASCII command

vi

BE1-851 Introduction

9289900990 Rev R