details on entering passwords from the HMI. Once access has been gained, the Edit LED will be

lighted and a cursor will appear in the first settings field on the screen.

3. Press the UP or DOWN scrolling key to select the desired setting. Some settings require entering

a number one character at a time. For example, to enter a 51 pickup as 7.3 amps, you would

press the UP pushbutton until the 7 is showing. Then, press the RIGHT pushbutton to move the

cursor over and press the UP pushbutton until the “

.” is showing. Then press the RIGHT

pushbutton to move the cursor over and press the UP pushbutton until the 3 is showing. Other

settings require scrolling through a list of selections. For example, you would move the cursor over

to the CRV field and then scroll through a list of available TCC curves.

4. Once all of the settings on the screen have been entered, press the Edit pushbutton a second time

and the settings will be validated. If the settings are in range, the screen will flash

CHANGES

SAVED, and the Edit LED will go out. If you want to abort the edit session without changing any

settings, press the Reset pushbutton before you press the Edit pushbutton the second time. The

screen will flash

CHANGES LOST and the Edit LED will go out.

Entering Passwords

If password security has been initiated for a function, the HMI will prompt you to enter a password when

the Edit pushbutton is pressed. To gain access, you must enter the appropriate password. A field of eight

asterisks appears with the cursor located under the leftmost character position. You can enter passwords

by performing the following procedure:

1. Press the UP or DOWN scrolling pushbuttons until the proper first character of the password

appears. Pressing the UP pushbutton scrolls through the alphabet and then the numbers in

ascending order. Pressing DOWN scrolls through the numbers and then the alphabet in

descending order.

2. Press the RIGHT scrolling pushbutton to move the cursor to the next character of the password

and select the appropriate character.

3. Continue the process until the entire password has been spelled out. If the password is less than

eight characters, leave the remaining asterisks in place instead of entering blanks.

4. Press the Edit pushbutton to enter the password. If the proper password has been entered, the

screen will flash

ACCESS GRANTED. If an incorrect password has been entered, the screen will

flash

ACCESS DENIED and the Edit LED will go out.

5. Once you gain access, it remains in effect for five minutes. As long as you continue to press the

Edit key for a function for which you have gained access, the five-minute timer will be refreshed

and you will not be prompted for a password.

Performing Control Operations

Control operations can be executed at Menu Branch 2, CONTROL of the HMI LCD. These functions allow

you to control the state of virtual switches, override logic, control the active setting group, and control the

state of output contacts. All of these functions work similarly to the process of entering settings in that you

press the Edit pushbutton for the action to be executed.
Figure 10-10 shows Virtual Switch 143 as an example of a virtual switch screen. See Section 4,

Protection and Control, for more details on the x43 and 101 functions. Table 10-3 describes each of the

locators shown on Figure 10-10. The user programmable label for this switch has been set to

RCL_DISABL. The TRUE (closed) state label has been set to DISABLD. The FALSE (open) state label

has been set to ENABLED. The logical mode for this application would be set to Mode 2 (On/Off switch).

Figure 10-10. Virtual Control Switch 143 Screen

9289900990 Rev R

BE1-851 Human-Machine Interface

10-9

Advertising