Output logic override control, Enabling logic override control, Pulsing an output contact – Basler Electric BE1-851 User Manual

Page 51: Holding an output contact open or closed, Returning an output contact to logic control, Output logic override control -9

Advertising
background image

Output Logic Override Control

Each output contact can be controlled directly using the select-before-operate output control function. The

virtual output logic expression that normally controls the state of an output contact can be overridden and

the contact pulsed, held open, or held closed. This function is useful for testing purposes. An alarm point

is available in the programmable alarm function for monitoring when the output logic has been overridden.

See Section 6, Reporting and Alarms, Alarms Function, for more information about programmable alarms.

Write access to control functions is required before using the select-before-operate control functions

through the HMI or ASCII command interface.

Enabling Logic Override Control

By default, logic override control is disabled. Output logic override must be enabled before the control can

be used. Enabling of the output logic override control is not possible at the front panel HMI or through

BESTCOMS. It can only be enabled through a communication port using the CS/CO-OUT=ena/dis

(control select/control operate-output override = enable/disable) command. The CS/CO-OUT command

only enables or disables override control of the output logic; it doesn’t enable or disable the outputs

themselves.

Pulsing an Output Contact

Pulsing BE1-851 outputs provides the same function as the push-to-energize feature of other Basler

Electric solid-state relays. This feature is useful when testing the protection and control system. When

pulsed, an output contact changes from the current state (as determined by the virtual output logic

expression) to the opposite state for 200 milliseconds. After 200 milliseconds, the output contact is

returned automatically to logic control.

Holding an Output Contact Open or Closed

Outputs can be forced to a closed (logic 1 or TRUE) state or to an open (logic 0 or FALSE) state. This

feature can be used to disable a contact during testing. Open or close logic override control is accessed

at Screen 2.4.1 of the HMI by entering a 0 for open or 1 for closed in the field for the output contact to be

controlled. Outputs are forced open or closed through a communication port by using the CS/CO-

OUTn=P0/1 (control select/control operate-output contact n-0/1) command.

Returning an Output Contact to Logic Control

When the output logic has been overridden and the contact is held in an open or closed state, it’s

necessary to manually return the output to logic control. Outputs are returned to logic control through

Screen 2.4.1 of the HMI. An L is entered in the field of the contact that is to be returned to logic control.

Outputs are returned to logic control through a communication port by using the CS/CO-OUTn=L (control

select/control operate-output contact n-0/1) command.
The output control commands require the use of select-before-operate logic. First, the command must be

selected using the CS-OUT command. After the command is selected, there is a 30 second window

during which the CO-OUT control command can be entered. The control selected and operation selected

syntax must match exactly or the command will be blocked. If the operate command isn’t entered within

30 seconds of the select command, the operate command will be blocked. An error message is returned

when a control command is blocked.
Output control commands are acted on immediately except when the ENA and DIS modes are used. ENA

and DIS output control command changes aren’t executed until saved with the EXIT command. Output

control status is saved in non-volatile memory and is maintained when the relay operating power is lost.

All relay responses in the following examples and throughout the manual are printed in Courier New

typeface.

1. Enable the output control feature.

>CS-OUT=ENA

OUT=ENA SELECTED

>CO-OUT=ENA

OUT=ENA EXECUTED

>E (exit)

Save Changes (Y/N/C)?

>Y (yes)

9289900990 Rev R

BE1-851 Input and Output Functions

3-9