Figure 14-24. BESTlogic Screen, Logic Select Tab

Virtual Outputs

You can assign a meaningful name or label to each virtual output. This makes sequential events reports

easier to analyze. To assign a meaningful label to Virtual Output VO6, click in the Label field and enter

the new name. Refer to Figure 14-25. Remember, VO6 does not have actual hardware output contacts.

Only VOA and VO1 through VO5 have hardware output contacts. To change the label for the True State,

click on the True State field and enter the new name. To change the label for the False State, click on the

False State field and enter the new name. To change the logic associated with VO6, click on the

BESTlogic button associated with VO6. Click on the logic input and program the logic variables that

define VO6. You may clear the existing programming by clicking on the Clear button or clicking on each

individual variable. The other 15 virtual outputs have the same function.

Figure 14-25. BESTlogic Screen, Virtual Outputs Tab

9289900990 Rev R

BE1-851 BESTCOMS™ Software