Table 6-6. breaker duty monitoring settings -13 – Basler Electric BE1-851 User Manual

Page 115

Advertising
background image

To connect the functions BLOCK logic input select the Logic button in the Block Accumulation Logic box.

The BESTlogic Function Element screen for Breaker Duty Monitoring will appear. See Figure 6-6. Then

select the BLOCK input button. The BESTlogic Expression Builder screen will open. Select the

expression type to be used. Then, select the BESTlogic variable or series of variables to be connected to

the input. Select Save when finished to return to the BESTlogic Function Element screen. For more

details of the BESTlogic Expression Builder, see Section 7, BESTlogic Programmable Logic. Select Done

when the settings have been completely edited.

Figure 6-6. BESTlogic Function Element Screen, Breaker Duty Monitoring

Table 6-6. Breaker Duty Monitoring Settings

Setting

Range/Purpose

Default

Mode

0 = Disabled
1 = Enabled

I

2 = Enabled

I2

0

100% Duty

Maximum

0 to 4.2e+7
The Dmax parameter represents the maximum duty that the breaker

contacts can withstand before needing service. Dmax is programmed in

primary amperes using exponential floating-point format.

0

Block

Accumulation

Logic

OR logic term (e.g., IN1 or VO7) that blocks the breaker monitoring logic

when TRUE (1). A setting of 0 disabled blocking (breaker operation are

no longer counted).

0


Example 1.

Make the following settings to the Breaker Duty Monitoring Function. Refer to Figure 6-5

and Figure 6-6.

Mode:

Enabled

I2

100% Duty Maximum:

2.000e+04

Block Accumulation Logic:

IN3

9289900990 Rev R

BE1-851 Reporting and Alarms

6-13