Figure 4-15. curve coefficients screen -17, O figure 4-15, N table 4-8 – Basler Electric BE1-851 User Manual

Page 73

Advertising
background image

Table 4-8. Definitions for Equations 4-1 and 4-2

Parameter

Description

Explanation

T

T

Time to trip

Time that the 51 function will take to time out and trip.

D

Time dial setting

Time dial setting for the 51 function.

M

Multiple of pickup

Measured current in multiples of pickup. The timing algorithm has a

dynamic range of 0 to 40 times pickup.

A

Coefficient specific

to selected curve

Affects the effective range of the time dial.

B

Coefficient specific

to selected curve

Affects a constant term in the timing equation. Has greatest effect

on curve shape at high multiples of tap.

C

Coefficient specific

to selected curve

Affects the multiple of PU where the curve would approach infinity if

allowed to continue below pickup. Has greatest effect on curve

shape near pickup.

N

Exponent specific

to selected curve

Affects how inverse the characteristics are. Has greatest effect on

curve shape at low to medium multiples of tap.

K

Constant

Characteristic minimum delay term.

T

R

Time to reset

Relevant if 51 function is set for integrating reset.

R

Coefficient specific

to selected curve

Affects the speed of reset when integrating reset is selected.

Curve coefficients can be entered using BESTCOMS. Alternately, curve coefficients can be entered using

the SP-CURVE (Settings Protection-programmable curve) command. Table 4-9 lists the programmable

curve settings.

Table 4-9. Programmable Time Current Characteristic Curve Coefficients

Setting

Range

Increment

Default

A Coefficient

0 to 600

0.0001

0.2663

B Coefficient

0 to 25

0.0001

0.0339

C Coefficient

0.0 to 1.0

0.0001

1.0000

N Coefficient

0.5 to 2.5

0.0001

1.2969

R Coefficient

0 to 30

0.0001

0.5000

Curve coefficients are entered by selecting the Curve Coefficients button on the 51 or 151 tab in the

Overcurrent screen (refer to Figure 4-14). The Curve Coefficients screen will appear. See Figure 4-15.

Enter the calculated values for each constant and select Done.

Figure 4-15. Curve Coefficients Screen

9289900990 Rev R

BE1-851 Protection and Control

4-17

Advertising