Table B-10. User Programmable Name Setting Command

ASCII Command

Function

HMI Screen

SN[-{var}[={name},{TRUE label},{FALSE label}]

Read/Set user programmable names.

N/A

Table B-11. Protection Setting Commands

ASCII Command

Function

HMI Screen

S{g}

Read all protection settings.

N/A

S{g}-x50T[{p}][={pu(A)}[,{td(m)}]]

Read/Set 50T pickup level and time

delay.

5.x.1.1 -

5.x.1.6

S{g}-x51[{p}][={pu(A)},{td(m)},{crv}]

Read/Set 51 pickup level, time delay, and

curve.

5.x.2.1 -

5.x.2.3

S{g}-{f}62[={td1},{td2}]

Read/Set 62 time delay.

5.x.3.1 -

5.x.3.2

S{g}-79[#][={td}]

Read/Set 79 time delay.

5.x.4.1 -

5.x.4.4

S{g}-79SCB[={step list}]

Read/Set 79 Sequence Controlled Block

output.

5.x.4.5

SP-BF[={time}[m/s/c]]

Read/Set the breaker failure timer

setting.

5.5.1.1

SP-CURVE[={A},{B},{C},{N},{R}]

Read/Set the user programmable 51

curve parameters.

N/A

SP-GROUP{g}=[{sw_time},{sw_level},{ret_time},

{ret_level},{prot_ele}]

Read/Program auxiliary setting group 1

operation.

N/A

SP-79ZONE[={zone pickup logic}]

Read/Set Zone Sequence Pickup Logic.

N/A

Table B-12. Global Command

ASCII Command

Function

HMI Screen

GS-PW[{t}[={password},{com ports(0/1/2)}]]

Read or change a password.

N/A

B-4

BE1-851 Command Cross-Reference

9289900990 Rev R