Reclosing, Breaker failure, Reclosing -11 – Basler Electric BE1-851 User Manual

Page 315: Breaker failure -11, Figure 14-13. reclosing screen -11

Advertising
background image

Reclosing

Pull down the Screens menu and select Reclosing or click on the Reclosing icon that is shown

at the right margin of this paragraph. This screen has no folder tabs. It is labeled Reclosing.
The reclosing function provides up to four reclosing attempts that can be initiated by a

protective trip or by one of the contact sensing inputs. (See Figure 14-13.) To set the actual reclose

sequence, first pull down the Time Units menu and set the units for time measurement. Notice that when

the Reclose 1 Time setting is zero, the Sequence Controlled Block (SCB), Trip 1 is grayed out. Set the

Reclose 1 Time for the first reclose time and the SCB window is now available. Enter the reclose times for

the remaining reclose attempts. The total time for all reclose attempts is cumulative. For example, the

second reclose attempt is the sum of Reclose 1 Time and Reclose 2 Time. Reclose three total time would

be the sum of the reclose time for three, two, and one. If you want to block the instantaneous or any other

protection element during reclose, check the SCB window or windows. If the 79C or 52 status is TRUE,

and the SCB is enabled (checked) for the next reclose attempt, the 79 SCB output becomes TRUE and

the output logic can be used to block the instantaneous element.
Set the reset time using the same unit of measure that was used for the reclosing attempts. Reset time is

how long you want the relay to remain reset before the relay returns to the initial state.
Set the maximum cycle time. Maximum cycle time limits the duration of a reclosing sequence as

determined from sequence initiation to automatic relay reset or lockout.

Figure 14-13. Reclosing Screen

Logic settings for the 79 reclosing function can be made by clicking on the BESTlogic button and with

your custom logic selected, select the mode and other input logic by using the Mode pull-down menu and

clicking on the logic inputs to set the logic.
To set the zone sequence coordination, click on the Zone-Sequence Logic button. When the Reclosing

dialog box opens, click on the logic diagram and set the logic.

Breaker Failure

Pull down the Screens menu and select Breaker Failure or click on the Breaker Failure icon

that is shown at the right margin of this paragraph. This screen has no folder tabs. It is labeled

Breaker Failure.
To set the time delay from when the breaker failure initiate is received and the trip output is asserted, first

pull down the Timer Setting Units menu (Figure 14-14) and set the units for time measurement. Then set

the Timer Setting Time.
9289900990 Rev R

BE1-851 BESTCOMS™ Software

14-11

Advertising