Table 13-4. pickup settings -4, Table 13-5. pickup ranges -4, Table 13-6. pickup settings -4 – Basler Electric BE1-851 User Manual

Page 292: Table 13-7. pickup ranges -4

Advertising
background image

Step 2:

Transmit the appropriate command from Table 13-4 to program the 50T pickup setting.

Table 13-4. Pickup Settings

Style Number

Commands

Phase

Neutral

x1xxxxx

S0-50TP=0.1A,0m

S0-50TN=0.1A,0m

x3xxxxx

S0-50TP=0.5A,0m

S0-50TN=0.1A,0m

x5xxxxx

S0-50TP=0.5A,0m

S0-50TN=0.5A,0m


Step 3:

Slowly ramp up the current applied at Phase A input until OUT1 closes. Verify that pickup

occurred within the acceptable range listed in Table 13-5.

Table 13-5. Pickup Ranges

Style

Number

Phase

Neutral

Low Limit

High Limit

Low Limit

High Limit

x1xxxxx

0.09 amps

0.11 amps

0.09 amps

0.11 amps

x3xxxxx

0.45 amps

0.55 amps

0.09 amps

0.11 amps

x5xxxxx

0.45 amps

0.55 amps

0.45 amps

0.55 amps


Step 4:

After pickup occurs, ramp the current down slowly until OUT1 opens. Dropout should occur

at 90% ±2% of the pickup current magnitude.

Step 5:

Transmit the appropriate command in Table 13-6 to reprogram the pickup setting.

Table 13-6. Pickup Settings

Style Number

Commands

Phase

Neutral

x1xxxxx

S0-50TP=1.0A,0m

S0-50TN=1.0A,0m

x3xxxxx

S0-50TP=5.0A,0m

S0-50TN=1.0A,0m

x5xxxxx

S0-50TP=5.0A,0m

S0-50TN=5.0A,0m


Step 6:

Slowly ramp up the current applied at the relay Phase A input until OUT1 closes. Verify that

pickup occurred within the acceptable range listed in Table 13-7.

Table 13-7. Pickup Ranges

Style

Number

Phase

Neutral

Low Limit

High Limit

Low Limit

High Limit

x1xxxxx

0.98 amps

1.02 amps

0.98 amps

1.02 amps

x3xxxxx

4.9 amps

5.1 amps

0.98 amps

1.02 amps

x5xxxxx

4.9 amps

5.1 amps

4.9 amps

5.1 amps

13-4

BE1-851 Testing and Maintenance

9289900990 Rev R