Reclosing, Reclosing -28, Figure 4-30. reclosing logic block -28 – Basler Electric BE1-851 User Manual

Page 84

Advertising
background image

At the top center of the screen is a pull-down menu labeled Logic. This menu allows viewing of the

BESTlogic settings for each preprogrammed logic scheme. User or custom logic must be selected on this

menu in order to allow changes to be made to the mode and inputs of the element.
To the right of the Logic pull-down menu is a pull-down menu labeled Settings. The Settings menu is used

to select the setting group that the element’s settings apply to. See Section 7, BESTlogic Programmable

Logic, Logic Schemes.
Using the pull-down menus and buttons, make the application appropriate settings to the Logic Timers

element. Table 4-14 summarizes the operating settings for General Purpose Logic Timers.

Table 4-14. Operating Settings for General Purpose Logic Timers

Setting

Range

Increment

Unit of Measure

Default

T1 Time,

T2 Time

0 to 999 ms

1

Milliseconds

0

0.1 to 9999 sec.

0.1 for 0.1 to 9.9 sec.

Seconds

1.0 for 10 to 9999 sec.

0 to 599,940 (60 Hz)

0 to 499,950 (50Hz)

Cycles

Time delays less than 10 cycles can be entered to the nearest 0.1 cycles through the HMI. All time

delays can be entered to the nearest 0.01 cycles from the ASCII command interface. Time delays entered

in cycles are converted to milliseconds or seconds. Increment precision after conversion is limited to that

appropriate for each of those units of measure.
Example 1.

Make the following operating settings to the 62 element. See Figure 4-29.

Logic:

User

Setting:

Group 0

Time Units:

ms

T1 Time:

100

T2 Time:

0

Retrieving General Purpose Logic Timers Status from the Relay

The status of each logic variable can be determined from the ASCII command interface by using the RG-

STAT (report general-status) command. Status cannot be determined using BESTCOMS. See Section 6,

Reporting and Alarms, General Status Reporting, for more information.

Reclosing

The BE1-851 reclosing function provides up to four reclosing attempts that can be initiated by a protective

trip or by one of the contact sensing inputs. The reclosers allow supervisory control and coordination of

tripping and reclosing with other system devices. Any of the four recloser shots can be used to select a

different setting group when the appropriate shot is reached in a reclosing sequence. This change in

setting groups allows changing protection

coordination during the reclosing

sequence. For example, you could have a

fast 51 curve on the first two trips in the

reclosing sequence and then switch to a

new group on the second reclose that

uses a slow 51 curve. Detailed

information about relay setting groups can

be found earlier in this section under the

heading of Setting Groups. Recloser

function block inputs and outputs are

shown in Figure 4-30 and are described in

the following paragraphs. An overall logic

diagram for the recloser function is shown

in Figure 4-38.

Figure 4-30. Reclosing Logic Block

4-28

BE1-851 Protection and Control

9289900990 Rev R