Retrieving reclosing status from the relay, Retrieving reclosing status from the relay -34 – Basler Electric BE1-851 User Manual

Page 90

Advertising
background image

Figure 4-37. BESTlogic Function Element Screen, Reclosing (Zone Sequence Logic)


Table 4-17 summarizes the settings for Zone-Sequence Coordination.

Table 4-17. Settings for Zone-Sequence Coordination

Function

Range/Purpose

Zone Pickup Logic

The zone sequence pickup logic defines which

logic elements should be considered zone

sequence pickups. Only OR (+) logic can be used –

no AND (∗) variables may be used.

Recloser zone-sequence coordination detects when a downstream recloser has cleared a fault and

increments the upstream 79 automatic reclose count to maintain a consistent count with the other

recloser. A fault is presumed cleared downstream when one or more protective functions pickup and

dropout with no trip occurring. If the zone pickup logic becomes TRUE and then FALSE without a trip

output operating, then the 79 automatic reclose counter should be incremented. The Max Cycle timer

resets the shot counter.

Retrieving Reclosing Status from the Relay

The status of each logic variable can be determined through the ASCII command interface using the RG-

STAT (report general-status) command. See Section 6, Reporting and Alarms, General Status Reporting,

for more information. The status cannot be determined using BESTCOMS.

Figure 4-38 (next page) illustrates an overall logic diagram for Reclosing.

4-34

BE1-851 Protection and Control