Table 13-16. pickup and timer settings -8, Table 13-17. timing ranges -8, Table 13-18. timing ranges -8 – Basler Electric BE1-851 User Manual

Page 296

Advertising
background image

Table 13-16. Pickup and Timer Settings

Style Number

Commands

Phase

Neutral

x1xxxxx

S0-50TP=1.0A,0.0m

S0-50TN=1.0A,0.0m

x3xxxxx

S0-50TP=5.0A,0.0m

S0-50TN=1.0A,0.0m

x5xxxxx

S0-50TP=5.0A,0.0m

S0-50TN=5.0A,0.0m

Step 3:

Apply the appropriate current value to the Phase A input and measure the time between the

application of current and OUT1 closing. Verify that the timing is within the acceptance range

stated in Table 13-17.

Table 13-17. Timing Ranges

Style

Number

Current/Frequency

Timing Range

Phase

Neutral

Low Limit

High Limit

x1xxxxx

1.05A/50 Hz

1.05A/50 Hz

0.0 sec

0.1 sec

x1xxxxx

1.05A/60 Hz

1.05A/60 Hz

0.0 sec

0.083 sec

x3xxxxx

5.25A/50 Hz

1.05A/50 Hz

0.0 sec

0.1 sec

x3xxxxx

5.25A/60 Hz

1.05A/60 Hz

0.0 sec

0.083 sec

x5xxxxx

5.25A/50 Hz

5.25A/50 Hz

0.0 sec

0.1 sec

x5xxxxx

5.25A/60 Hz

5.25A/60 Hz

0.0 sec

0.083 sec


Step 4:

Apply the appropriate current value to the Phase A input and measure the time between the

application of current until OUT1 closes. Verify that the timing is within the acceptance range

stated in Table 13-18.

Table 13-18. Timing Ranges

Style

Number

Current/Frequency

Timing Range

Phase

Neutral

Low Limit

High Limit

x1xxxxx

1.5A/50 Hz

1.5A/50 Hz

0.0 sec

0.04 sec

x1xxxxx

1.5A/60 Hz

1.5A/60 Hz

0.0 sec

0.033 sec

x3xxxxx

7.5A/50 Hz

1.5A/50 Hz

0.0 sec

0.04 sec

x3xxxxx

7.5A/60 Hz

1.5A/60 Hz

0.0 sec

0.033 sec

x5xxxxx

7.5A/50 Hz

7.5A/50 Hz

0.0 sec

0.04 sec

x5xxxxx

7.5A/60 Hz

7.5A/60 Hz

0.0 sec

0.033 sec


Step 5:

Apply the appropriate current value to the Phase A input and measure the time between the

application of current and OUT1 closing. Verify that the timing is within the acceptance range

stated in Table 13-19.

13-8

BE1-851 Testing and Maintenance

9289900990 Rev R

Advertising