Table 8-15. Feeder_3 Virtual Switches Logic

Switch

Purpose

Mode

Label

State Labels

True

False

43

Automatic setting group change

logic auto/manual switch.

2 (On/Off) SETGRP_MAN

MANUAL

AUTO

143

Disable recloser when virtual

switch is closed.

2 (On/Off)

RCL_DISABL

DISABLD ENABLED

243

Disable neutral and negative-

sequence, 50 and 51 protection

when virtual switch is closed.

2 (On/Off)

N&Q_DISABL

DISABLD ENABLED

343

Put the relay in test mode so that

reclosing and breaker failure are

disabled when virtual switch is

closed.

2 (On/Off) TESTENABLE TSTMODE NORMAL

101

Virtual Control Switch to trip bus

breaker.

1 (Enable)

N/A

N/A

N/A

Table 8-16. Feeder_3 Virtual Outputs

Output

Purpose

Description

Label

State Labels

True

False

VOA

(OUTA)

Alarm Output Contact.

Change state of alarm contact

when relay failure or major

programmable alarm is TRUE.

ALARM

ACTIVE

NORMAL

BESTlogic Expression: VOA=ALMMAJ

VO1

(OUT1)

Breaker trip contact.

Trip breaker when protective

trip expression is TRUE or

when breaker failure is initiated

or when virtual breaker control

switch is operated to trip

BKR_TRIP

TRIP

NORMAL

BESTlogic Expression: VO1=VO11+BFPU+101T

VO2

(OUT2)

Breaker close contact.

Close breaker when recloser

close output it TRUE or when

virtual breaker control switch is

operated to close.

BKR_CLOSE

CLOSE

NORMAL

BESTlogic Expression: VO2=79C+101C

VO3

(OUT3)

Enable backup of relay

by upstream relay.

Hold output closed if relay is

not out of service because it is

in test mode and it is not out of

service due to relay failure

IN_SERVICE

NORMAL BACKUP

BESTlogic Expression: VO3=IN4*/343

VO4

(OUT4)

Block upstream

instantaneous elements

when relay is picked up

for high-speed bus

overcurrent protection

logic.

Block upstream instantaneous

elements when the protective

pickup expression is TRUE

and the relay is not in test

mode and the breaker has not

failed.

BLK_UPSTRM BLOCKED NORMAL

BESTlogic Expression: VO4=VO12*/VO5*IN4*/343

8-30

BE1-851 Application