Basler Electric BE1-851 User Manual

Page 184

Advertising
background image

be controlled by a pole of a standard external test switch that is opened with the rest of the test switch

poles.
The logic expression for test mode drives virtual output 15 (VO15). This virtual output is alarm bit #23 in

the programmable alarm mask. It can be masked to drive an alarm LED to provide indication when the

relay is in test mode.

Contingency Operation - Backup Protection for Feeder Breaker Failure

OUT5 is configured as the breaker failure trip output. OUT5 can be wired to trip the bus breaker or a

lockout relay. The breaker failure pickup (BFPU) output trips the feeder breaker directly via output 1 to

provide a breaker re-trip signal for added security.
Initiation of the BF function block by external relays is not accommodated in this scheme. IN2, IN3, or IN4

can be programmed to provide this function or Feeder_4 logic may be used. The breaker failure function

block is initiated by a protective trip. This function block has an independent fast drop out phase and

ground current detector that detects opening and stops timing. An open breaker is detected when the

current drops below 10% of nominal.
Setting the time delay at zero disables the BF function block. This permits the traditional radial system

backup scheme of coordinated relays tripping different breakers.
Feeder_3 logic stops the block signal to allow the bus relay to trip the bus breaker through its 50T

elements if a direct trip is not desired. This provides clearing of the fault on the circuit with the failed

breaker in feeder relay breaker failure time (or bus relay 50T time; whichever is greater) instead of the

bus relay 51 time; but is limited by the sensitivity constraints of the bus relay.

Contingency Operation - Backup Protection for Feeder Relay Out-of-Service

When the relay is out of service or it has failed, OUT3 opens to signal the upstream relays providing

backup protection. OUT3 operates in a fail-safe mode; the output is closed during normal operation and

open during a relay failure. This provides backup mode signaling when the feeder relay is extracted from

the case.
Backup for relay failure can be implemented using the BUS and BACKUP preprogrammed logic schemes.

These logic schemes are described later in this section.

Table 8-13. Feeder_3 Contact Sensing Input Logic

Input

Purpose

Name Label

State Labels

Energized

De-Energized

IN1

52b Breaker Status.

BREAKER

OPEN

CLOSED

IN2

Enable recloser when IN2 is energized. RCL_ENABLE

ENABLED

DISABLD

IN3

Enable neutral and negative-sequence,

50 and 51 protection when IN3 is

energized.

N&Q_ENABLE

ENABLED

DISABLD

IN4

Put the relay in test mode so that

reclosing and breaker failure are

disabled when IN4 is de-energized.

TESTDISABL

NORMAL

TSTMODE







8-28

BE1-851 Application

9289900990 Rev R

Advertising