Outputs

BE1-851 relays have five general-purpose output contacts (OUT1 through OUT5) and one fail-safe,

normally open/normally closed, alarm output contact (OUTA). Each output is isolated and rated for

tripping duty. OUT1 through OUT5 are “Form A” (normally open) and OUTA is “Form A or B” (normally

open or closed depending on BE1-851 style number, case option).

Hardware Outputs and Virtual Outputs

Output contacts OUT1 through OUT5 and OUTA are driven by BESTlogic™ expressions for VO1 through

VO5 (Virtual Outputs 1 through 5) and VOA (Virtual Output A). The use of each output contact is

completely programmable so you can assign meaningful labels to each output and to the logic 0 and logic

1 states of each output. Section 7, BESTlogic Programmable Logic, has more information about

programming output expressions in your programmable logic schemes.
A virtual output (VOn) exists only as a logical state inside the relay. A hardware output is a physical output

relay contact. BESTlogic expressions for VO1 through VO5 (Virtual Outputs 1 through 5) and VOA

(Virtual Output A) drive output contacts OUT1 through OUT5 and OUTA. The state of the output contacts

can vary from the state of the output logic expressions for three reasons:

The relay trouble alarm disables all hardware outputs.

The programmable hold timer is active.

The select-before-operate function overrides a virtual output.


Figure 3-6 shows a diagram of the output contact logic for the general-purpose output contacts. Figure

3-7 illustrates the output contact logic for the fail-safe alarm output contact.

Figure 3-6. Output Logic, General Purpose Output Contacts

Figure 3-7. Output Logic, Fail-Safe Alarm Output Contact

Retrieving Output Status

The relay’s outputs can be monitored from the Metering screen. To open the Metering screen select

Metering from the Reports pull-down menu. To begin viewing the relay’s metered values, select the Start

Polling button in the bottom right hand corner of the screen.

0.200

Sec

0

Sec

OR

ONE SHOT

TIMER

AND

OUT[A]

HARDWARE

OUTPUT

OUTPUT

STATUS

AND

AND

OR

Control Override (0/1)

Override State (0/1)

Hold State (0/1)

VO[A]

VIRTUAL OUTPUT

CONTROLLED BY SL-VO[n]

LOGIC EQUATION

HOLD ENA

(SG-HOLD COMMAND)

OUTPUT CONTROL

(CO-OUT COMMAND)

ALMREL

D2647-19

03-13-06

NOT

9289900990 Rev R