Example 1.

Make the following BESTlogic settings to the Breaker Failure element. See Figure 4-19.

Mode:

Enable

Initiate:

VO1

Block:

IN4

Operating Settings for Breaker Failure Protection

Operating settings are made using BESTCOMS. Figure 4-20 illustrates the BESTCOMS screen used to

select operational settings for the Breaker Failure element. To open the Breaker Failure screen, select

Breaker Failure from the Screens pull-down menu. Alternately, settings may be made using the SP-BF

ASCII command or from the HMI interface using Screen 5.5.1.1.

Figure 4-20. Breaker Failure Screen


At the top center of the screen is a pull-down menu labeled Logic. This menu allows viewing of the

BESTlogic settings for each preprogrammed logic scheme. User or custom logic must be selected on this

menu in order to allow changes to be made to the mode and inputs of the element. See Section 7,

BESTlogic Programmable Logic, Logic Schemes.
To the right of the Logic pull-down menu is a text box labeled Settings. The word “Global” appears in the

text box, indicating the element is not assigned to any setting group. The operating settings for the

Breaker Failure element consist of a single time delay (Time). The time delay can be set in milliseconds,

seconds, or cycles. The default is milliseconds if no unit of measure is specified. The minimum timing

resolution is to the nearest quarter-cycle. A time delay setting of zero makes the element instantaneous

with no intentional time delay.
If the time delay settings are made in cycles, they are converted to seconds or milliseconds before being

stored. This conversion is based on the nominal frequency setting stored in EEPROM. See Section 3,

Input and Output Functions, Current Measurement Functions, for more information on this setting. If the

user is changing the nominal frequency setting from the default (60 Hz) and setting the time delays in

cycles, the frequency setting should be entered and saved to EEPROM first by entering E;Y.
Using the pull-down menus and buttons, make the application appropriate settings to the Breaker Failure

element.
Table 4-12 summarizes the operating settings for Breaker Failure Protection.

4-22

BE1-851 Protection and Control

9289900990 Rev R