Targets, Targets -21, Table 6-10. fault recording trigger settings -21 – Basler Electric BE1-851 User Manual

Page 123: Table 6-11. targets as displayed -21

Advertising
background image

Table 6-10. Fault Recording Trigger Settings

Setting

Purpose

Default

TRIPPED

Logic expression used to define Trip fault reporting condition. When

this expression becomes TRUE (1), it triggers data recording and

illuminates the Trip LED.

VO11+BFT

PICKED UP

Logic expression used to define Pickup fault reporting condition.

When this expression becomes TRUE (1), it initiates the pickup

timing sequence and the Trip LED will flash on and off.

VO12+BFPU

LOGIC

Logic expression used to define the trigger for fault reporting when

relay is not picked up. When this expression is TRUE (1), fault

reporting is triggered.

0


Example 1.

Make the following settings to the fault reporting function. Refer to Figure 6-12.

TRIPPED:

BFT+VO11

PICKED UP: VO12

LOGIC:

0

Targets

Each protective function logs target information to the fault reporting function when a trip condition occurs

and the trip output of the function block becomes TRUE (refer to Figure 6-8 and Table 6-8, call-out B).

Target information can be viewed and reset at the HMI and through the communication ports.
Target logging for a protective function can be disabled if the function is used in a supervisory or

monitoring capacity. The following paragraphs describe how the relay is programmed to define which

protective functions log targets. Table 6-11 lists the IEEE Device Number and the definition of the targets

displayed.

Table 6-11. Targets as Displayed

IEEE Device

Number

Definition

50 ABC

Phase Instantaneous Overcurrent

50 N

Neutral Instantaneous Overcurrent

50 Q

Negative-Sequence Instantaneous Overcurrent (Sensing Input type H, only)

150 ABC

Second Phase Instantaneous Overcurrent

150 N

Second Neutral Instantaneous Overcurrent

150 Q

Second Negative-Sequence Instantaneous Overcurrent (Sensing Input type H, only)

250 N

Third Neutral Instantaneous Overcurrent (Sensing Input type G, only)

350 N

Fourth Neutral Instantaneous Overcurrent (Sensing Input type G, only)

51 ABC

Phase Inverse Time Overcurrent

51 N

Neutral Inverse Time Overcurrent

51 Q

Negative-Sequence Inverse Time Overcurrent (Sensing Input type H, only)

151 N

Second Neutral Time Overcurrent (Sensing Input type G, only)

62

General Purpose Logic Timer

162

Second General Purpose Logic Timer

262

Third General Purpose Logic Timer (Available when style option 1 is V or W.)

362

Fourth General Purpose Logic Timer (Available when style option 1 is V or W.)

BF

Breaker Failure

9289900990 Rev R

BE1-851 Reporting and Alarms

6-21