Reading logic settings, Reading logic settings -6 – Basler Electric BE1-851 User Manual

Page 248

Advertising
background image

SG-FREQ=60

SG-HOLDA=0; SG-HOLD1=1; SG-HOLD2=1; SG-HOLD3=0

SG-HOLD4=0; SG-HOLD5=1

SG-ID=BE1-851,SUBSTATION_1

SG-IN1= 4, 16; SG-IN2= 4, 16; SG-IN3= 4, 16; SG-IN4= 4, 16

SG-PHROT=1

SG-SCREEN1=4.5; SG-SCREEN2=1.5.6; SG-SCREEN3=4.3.1; SG-SCREEN4=1.1

SG-SCREEN5=3.1; SG-SCREEN6=3.2; SG-SCREEN7=4.4; SG-SCREEN8=4.4.3

SG-SCREEN9=4.4.3.1; SG-SCREEN10=4.4.3.2;SG-SCREEN11=4.4.3.3;SG-SCREEN12=4.4.3.4

SG-SCREEN13=4.4.3.5;SG-SCREEN14=0; SG-SCREEN15=0; SG-SCREEN16=0

SG-SGCON= 5

SG-DATADUMP= 0

SG-

TARG=50TA/50TB/50TC/50TN/62/162/BF/150TA/150TB/150TC/150TN/250TN/350TN/51A/51B/51C/

51N/262/362/151N,0

SG-TRIGGER=BFT+VO11,BFPU+VO12,0

SN Command
Purpose:

Read/Set User Programmable Names

Syntax:

SN[-{var}[={name},{TRUE label},{FALSE label}]

Example:

SN or SN-VO1=TRIP,CLOSED,OPEN or SN-IN1=BREAKER,OPEN,CLOSED


SN Command Example:

Read the programmed labels for the alarm output (OUTA).

>SN-VOA

VOA_LABEL,TRUE,FALSE


S<g> Command

Purpose:

Read all Protection settings

Syntax:

S{g} where g=setting group 0-3 or # for all groups

Example:

S# or S0 or S1


S<g> Command Example:

Obtain a list of settings for settings group 2.

>S2

S2-50TP=0.00, 0m; S2-50TN=0.00, 0m; S2-50TQ=0.00, 0m

S2-150TP=0.00, 0m; S2-150TN=0.00, 0m; S2-150TQ=0.00, 0m

S2-51P=0.00,0.0,V2; S2-51N=0.00,0.0,V2; S2-51Q=0.00,0.0,V2

S2-62= 0m, 0m

S2-162= 0m, 0m

S2-791= 0m; S2-792= 0m; S2-793= 0m; S2-794= 0m

S2-79R= 10s; S2-79F=1.0s; S2-79M= 60s

S2-79SCB=0

SP-79ZONE=0

SP-BF= 0m

SP-CURVE= 0.2663, 0.0339, 1.0000, 1.2969, 0.5000

SP-GROUP1= 0, 0, 0, 0,51P; SP-GROUP2= 0, 0, 0, 0,51P

SP-GROUP3= 0, 0, 0, 0,51P

Reading Logic Settings

The SL command is used to view the names of available logic schemes in memory. It also will return all of

the logic equations for a specific logic scheme.
SL Command
Purpose:

Obtain Setting Logic Information

Syntax:

SL:[{name}]

Example:

SL, SL: or SL:BASIC-OC

Comments:

No password access is required to read settings.

11-6

BE1-851 ASCII Command Interface

9289900990 Rev R

Advertising