General specifications, Ac current inputs, 5 ampere ct – Basler Electric BE1-851 User Manual

Page 25: 1 ampere ct, Analog to digital converter, Power supply, Option 1, Option 2, Option 3, Frequency range

Advertising
background image

General Specifications

AC Current Inputs
5 Ampere CT

Continuous Rating .......................................................... 20 A

One Second Rating ........................................................ 400 A
For other current levels, use the formula: I = (K/t)

1/2

where t = time in seconds, K = 160,000 (S1 case);

90,000 (H1/F1 case).
Begins to Clip (Saturate) ................................................ 150 A

Burden ............................................................................ 0.004 Ω or less at 5 A

1 Ampere CT

Continuous Rating .......................................................... 4 A

One Second Rating ........................................................ 80 A
For other current levels, use the formula: I = (K/t)

1/2

where t = time in seconds, K = 6,400.

Begins to Clip (Saturate) ................................................ 30 A

Burden ............................................................................ 0.01 Ω or less at 1 A

Analog to Digital Converter

Type ................................................................................ 16-bit

Sampling Rate ................................................................ 24 samples per cycle

Power Supply
Option 1

48, 110, and 125 Vdc ..................................................... Range 35 to 150 Vdc

67, 110, and 120 Vac ..................................................... Range 55 to 135 Vac

Option 2

110, 125, and 250 Vdc ................................................... Range 90 to 300 Vdc

110, 120, and 240 Vac ................................................... Range 90 to 270 Vac

Option 3

24 Vdc ............................................................................. Range 17 to 32 Vdc

Frequency Range

Options 1 and 2 only ....................................................... 40 to 70 Hz

Burden

Options 1, 2, and 3: ........................................................ 6 W continuous, 8 W maximum with all outputs

energized

Output Contacts

Make and Carry for Tripping Duty .................................. 30 A for 0.2 seconds per IEEE C37.90; 7 A

continuous

Break Resistive or Inductive ........................................... 0.3 A at 125 or 250 Vdc (L/R = 0.04 maximum)

9289900990 Rev R

BE1-851 General Information

1-9