Basler Electric BE1-851 User Manual

Page 187

Advertising
background image

Output

Purpose

Description

Label

State Labels

True

False

VO5

(OUT5)

Breaker failure trip

contact.

Trip backup if breaker failure

protection times out.

BKR_FAIL

TRIP

NORMAL

BESTlogic Expression: VO5=BFT

VO6

None

N/A

VO6

TRUE

FALSE

BESTlogic Expression: VO6=0

VO7

None

N/A

VO7

TRUE

FALSE

BESTlogic Expression: VO7=0

VO8

None

N/A

VO8

TRUE

FALSE

BESTlogic Expression: VO8=0

VO9

Recloser drive to lockout

expression.

Drive recloser to lockout to

disable it when IN2 is de-

energized or Virtual Switch

143 is closed or when the

breaker virtual control switch is

in the after trip state or if the

breaker fails or when the high

set instantaneous element

trips.

RCL_DTL

DTL

NORMAL

BESTlogic Expression: VO9=/IN2+143+VO5+150TPT+150TNT+150TQT

VO10

Breaker failure initiate

expression.

Initiate breaker failure timing

when protective trip expression

is TRUE.

BFI

INI

NORMAL

BESTlogic Expression: VO10=VO11

VO11

Protective Trip

Expression.

TRUE when any 50, 150, or 51

element times out.

PROT_TRIP

TRIP

NORMAL

BESTlogic Expression: VO11=50TPT+50TNT+50TQT+150TPT+150TNT+150TQT+51PT+51NT+51QT

VO12

Protection Picked Up

Expression.

TRUE when any 50, 150, or 51

element picks up.

PROT_PU

PU

NORMAL

BESTlogic Expression:

VO12=50TPPU+50TNPU+50TQPU+150TPPU+150TNPU+150TQPU+51PPU+51NPU+51QPU

VO13

Alarm Mask 21.

N/A

VO13

TRUE

FALSE

BESTlogic Expression: VO13=0

VO14

Alarm Mask 22.

N/A

VO14

TRUE

FALSE

BESTlogic Expression: VO14=0

VO15

Alarm bit #23 indication

that the relay is in test

mode, breaker failure is

disabled, and reclosing is

disabled.

TRUE if IN4 is de-energized or

if Virtual Switch 343 is closed.

TEST_MODE

TEST

NORMAL

BESTlogic Expression: VO15=/IN4+343

9289900990 Rev R

BE1-851 Application

8-31