SP-79ZONE Command

Purpose:

Read/Set 79 Zone Sequence Logic

Syntax:

SP-79ZONE[={zone pickup logic}]

Example:

SP-79ZONE or SP-79ZONE=50TPPU+50TNPU+150TPPU+150TNPU

Reference:

Section 4, Protection and Control, Reclosing

SP-BF Command

Purpose:

Read/Set the Breaker Failure Timer Setting

Syntax:

SP-BF[={time}[m/s/c]] where m=msec,s=sec,c=cycle

Example:

SP-BF or SP-BF=50m or SP-BF=3c

Reference:

Section 4, Protection and Control, Breaker Failure Protection

SP-CURVE Command

Purpose:

Read/Set the user programmable 51 curve parameters

Syntax:

SP-CURVE[={A},{B},{C},{N},{R}]

Example:

SP-CURVE or SP-CURVE=1.0,0,0,2.5,0

Reference:

Section 4, Protection and Control, Overcurrent Protection

SP-GROUP Command

Purpose:

Read/Program auxiliary setting group 1-3 operation

Syntax:

SP-GROUP{g}=[{sw_time},{sw_level},{ret_time},{ret_level},{prot_ele}]

Example:

SP-GROUP, SP-GROUP1=10,75,10,50,51P or SP-GROUP3=0,0,0,0,793

Reference:

Section 4, Protection and Control, Setting Groups

Global Commands

GS-PW Command

Purpose:

Read/Set Password and password access port(s)

Syntax:

GS-PW[{t}[={password},{com ports(0/1/2)}]] where t=G/S/C/R

Example:

GS-PWG=TEST,0 or GS-PWS=XYZ,1/2

Reference:

Section 9, Security