Hardware and software version, Hardware and software version -34 – Basler Electric BE1-851 User Manual

Page 136

Advertising
background image

Figure 6-21. BESTlogic Function Element Screen Alarm Reset Logic

BESTlogic™ Elements Controlled by Programmable Alarms

Major, Minor, and Logic programmable alarm settings drive BESTlogic variables ALMMAJ, ALMMIN, and

ALMLGC. These variables can be used in logic expressions to control logic when the alarm is active. For

example, these variables could be used to actuate an output relay to signal a SCADA RTU that an alarm

condition exists.

Hardware and Software Version

Hardware and software version reporting is used to determine what style chart selection are included in

the relay, the relay serial number and the version of the embedded software (firmware).
Style and serial number information is contained on the label on the front panel. Embedded software

information can be obtained at HMI Screen 4.6. The information of Screen 4.6 is also displayed briefly

when operating power is applied to the relay.
A software and hardware version report can be obtained through BESTCOMS. Alternately it can be

obtained using the RG-VER ASCII command.
To obtain the relay’s version report through BESTCOMS, select Download Settings from Device from the

Communications menu. Downloaded settings from the relay will overwrite any settings you have made in

BESTCOMS. The relay will ask you to save your current file before continuing the download.
To view the version of the relay after the download completes, select General Operation from the Screens

menu. Then select the General Information tab (see Figure 6-1). The General Information tab displays all

of the version information about the relay.





6-34

BE1-851 Reporting and Alarms

9289900990 Rev R

Advertising