Table 13-19. Timing Ranges

Style

Number

Current/Frequency

Timing Range

Phase

Neutral

Low Limit

High Limit

x1xxxxx

5.0A/50 Hz

5.0A/50 Hz

0.0 sec

0.025 sec

x1xxxxx

5.0A/60 Hz

5.0A/60 Hz

0.0 sec

0.021 sec

x3xxxxx

25.0A/50 Hz

5.0A/50 Hz

0.0 sec

0.025 sec

x3xxxxx

25.0A/60 Hz

5.0A/60 Hz

0.0 sec

0.021 sec

x5xxxxx

25.0A/50 Hz

25.0A/50 Hz

0.0 sec

0.025 sec

x5xxxxx

25.0A/60 Hz

25.0A/60 Hz

0.0 sec

0.021 sec


Step 6:

Transmit the appropriate command in Table 13-20 to program the pickup setting.

Table 13-20. Pickup Settings

Style Number

Commands

Phase

Neutral

x1xxxxx

S0-50TP=1.0A,5s

S0-50TN=1.0A,5s

x3xxxxx

S0-50TP=5.0A,5s

S0-50TN=1.0A,5s

x5xxxxx

S0-50TP=5.0A,5s

S0-50TN=5.0A,5s


Step 7:

Apply the appropriate current value to the Phase A input and measure the time between the

application of current and OUT1 closing. Verify that the timing is within the acceptance range

stated in Table 13-21.

Table 13-21. Pickup Ranges

Style

Number

Current/Frequency

Timing Range

Phase

Neutral

Low Limit

High Limit

x1xxxxx

1.05A/50 Hz

1.05A/50 Hz

4.85 sec

5.35 sec

x1xxxxx

1.05A/60 Hz

1.05A/60 Hz

4.833 sec

5.333 sec

x3xxxxx

5.25A/50 Hz

1.05A/50 Hz

4.85 sec

5.35 sec

x3xxxxx

5.25A/60 Hz

1.05A/60 Hz

4.833 sec

5.333 sec

x5xxxxx

5.25A/50 Hz

5.25A/50 Hz

4.85 sec

5.35 sec

x5xxxxx

5.25A/60 Hz

5.25A/60 Hz

4.833 sec

5.333 sec


Step 8:

Repeat Steps 2 through 7 for the Phase B input.

Step 9:

Repeat Steps 2 through 7 for the Phase C input.

Step 10:

Repeat Steps 2 through 7 for the Neutral input.



9289900990 Rev R

BE1-851 Testing and Maintenance