User programmable name setting command, Protection setting commands, User programmable name setting command -17 – Basler Electric BE1-851 User Manual

Page 259: Protection setting commands -17

Advertising
background image

SL-VO Command

Purpose:

Read/Set Output Logic

Syntax:

SL-VO[x[={Boolean equation}]] where x is 1 - 15 or A

Example:

SL-VO or SL-VO1=50TPT+50TNT+51PT+51NT+101T or SL-VO2=101C+79C*/O2

Reference:

Section 7, BESTlogic Programmable Logic, Working With Programmable Logic

User Programmable Name Setting Command

SN Command

Purpose:

Read/Set User Programmable Names

Syntax:

SN[-{var}[={name},{TRUE label},{FALSE label}]

Example:

SN or SN-VO1=TRIP,CLOSED,OPEN or SN-IN1=BREAKER,OPEN,CLOSED

Reference:

Section 7, BESTlogic Programmable Logic, User Input and Output Logic Variable Names

Protection Setting Commands

S<g> Command

Purpose:

Read all Protection settings

Syntax:

S{g} where g=setting group 0-3 or # for all groups

Example:

S# or S0 or S1

Reference:

Section 11, ASCII Command Interface, Settings (S) Command Descriptions

S<g>-50T Command

Purpose:

Read/Set x50T pickup level and time delay where x = blank or 1

Syntax:

S{g}-x50T[{p}][={pu(A)}[,{td(m)}]] where g = 0-3, p = P/N/Q

Example:

S0-50T or S1-50TP=25,0 or S1-150TN=3,20

Reference:

Section 4, Protection and Control, Overcurrent Protection

S<g>-51 Command

Purpose:

Read/Set 51 pickup level, time delay and curve where x = blank or 1

Syntax:

S{g}-x51[{p}][={pu(A)},{td(m)},{crv}] where p=P/N/Q, g=0-3

Example:

S0-51 or S0-51P=7.5,6.5,S1 or S1-51N=3,2.0,S1

Reference:

Section 4, Protection and Control, Overcurrent Protection

S<g>-62 Command

Purpose:

Read/Set 62 Time Delay

Syntax:

S{g}-{f}62[={td1},{td2}] where td suffix m=msec,s=sec,c=cy

Example:

S0-62=500m,200m or S0-62=0.5s,0.2s or S2-162=30c,12c

Reference:

Section 4, Protection and Control, General Purpose Logic Timers (62/162)

S<g>-79 Command

Purpose:

Read/Set 79 Time Delay

Syntax:

S{g}-79[#][={td}] where suffix m=msec,s=sec,c=cy

Example:

S0-791=100m or S0-792=0.5s or S0-793=60c

Reference:

Section 4, Protection and Control, Reclosing

S<g>-79SCB Command

Purpose:

Read/Set 79 Sequence Controlled Block Output

Syntax:

S{g}-79SCB[={step list}] where g=0,1,2,3

Example:

S0-79SCB=2/4

Reference:

Section 4, Protection and Control, Reclosing




9289900990 Rev R

BE1-851 ASCII Command Interface

11-17