Table 8-28. BACKUP Virtual Outputs

Output

Purpose

Description

Label

State Labels

True

False

VOA

(OUTA)

Alarm Output Contact.

Change state of alarm contact

when relay failure or major

programmable alarm is TRUE.

(Style dependent.)

ALARM

ACTIVE NORMAL

BESTlogic Expression: VOA=ALMMAJ

VO1

(OUT1)

Bus breaker trip.

Trip breaker for virtual control

switch trip OR for 51 trip or

when breaker failure is picked

up. Close OUT1 for any trip

when in test mode.

BKR_TRIP

TRIP

NORMAL

BESTlogic Expression: VO1=101T+VO8+BFPU+VO11*VO15

VO2

(OUT2)

Bus breaker close.

Close breaker when virtual

breaker control switch is

operated to close.

BKR_CLOSE

CLOSE NORMAL

BESTlogic Expression: VO2=101C

VO3

(OUT3)

Signal relay on bus

source that is using BUS

logic that feeder relay is

out of service.

Feeder relay is out of service

as indicated by contact open

from the feeder relays.

BACKUPMODE BACKUP NORMAL

BESTlogic Expression: VO3=/IN2

VO4

(OUT4)

Bus fault trip (86B).

Trip bus breaker via lockout for

bus faults (50T with 18-20

cycles delay) when not in test

mode.

BUS_TRIP

TRIP

NORMAL

BESTlogic Expression: VO4=VO9*/VO15

VO5

(OUT5)

Breaker failure trip

contact.

Trip backup if breaker failure

protection times out.

BKR_FAIL

TRIP

NORMAL

BESTlogic Expression: VO5=BFT

VO6

N/A

N/A

VO6

TRUE

FALSE

BESTlogic Expression: VO6=0

VO7

N/A

N/A

VO7

TRUE

FALSE

BESTlogic Expression: VO7=0

VO8

Time overcurrent trip.

TRUE if any of the time

overcurrent elements trip.

51_TRIP

TRIP

NORMAL

BESTlogic Expression: VO8=51PT+51NT+51QT

VO9

Instantaneous

overcurrent trip.

TRUE if any of the

instantaneous overcurrent

elements trip.

50_TRIP

TRIP

NORMAL

BESTlogic Expression: VO9=50TPT+50TNT+50TQT

VO10

Breaker failure initiate

expression.

Initiate breaker failure timing

when protective trip expression

is TRUE or when external

initiate contact is sensed and

any of the fault detectors is

picked up.

VO10

INI

NORMAL

BESTlogic Expression: VO10=0

9289900990 Rev R

BE1-851 Application