Real-Time Clock

Accuracy ......................................................................... 1 second per day at 25°C (free running) or ±2

milliseconds (with IRIG synchronization)

Resolution ....................................................................... 1 millisecond

Date and Time Setting Provisions .................................. Front panel, communications port, and IRIG. Leap

year correction provided.

Clock Power Supply Holdup Capacitor........................... 8 to 24 hours, depending on conditions

Clock Power Supply Holdup Battery............................... Greater than 5 years

Backup Battery (Optional) .............................................. Lithium battery 3.6 Vdc, 0.95 AH,

Basler Electric p/n: 9318700012 or

Applied Power p/n: BM551902

Communication Ports
Interface

Front RS-232 .................................................................. 300 to 19,200 baud, 8N1, full duplex

Rear RS-232 ................................................................... 300 to 19,200 baud, 8N1, full duplex

Rear RS-485 ................................................................... 300 to 19,200 baud, 8N1, half duplex

Display

Type ................................................................................ Two line, 16 characters alphanumeric LCD (liquid

crystal display) with light emitting diode (LED)

backlight.

Operating Temperature .................................................. −40°C (−40°F) to +70°C (+158°F)

Display contrast may be impaired at temperatures

below −20°C (−4°F).

Isolation

All circuits to Ground ...................................................... 2,828 Vdc (excludes communication ports)

Input Circuits to Output Circuits ...................................... 2,000 Vac or 2,828 Vdc

Communication Ports to Ground .................................... 700 Vdc for one minute

Surge Withstand Capability
Oscillatory

Qualified to IEEE C37.90.1-2002, Standard Surge Withstand Capability (SWC) Tests for Protective

Relays and Relay Systems.

Fast Transient

Qualified to IEEE C37.90.1-2002, Standard Surge Withstand Capability (SWC) Tests for Protective

Relays and Relay Systems.

Radio Frequency Interference (RFI)

Type tested using a five-watt, hand-held transceiver in the ranges of 144 and 440 MHz with the antenna

placed six inches from the relay. Qualified to C37.90.2-1995, Standard For Withstand Capability Of Relay

Systems To Radiated Electromagnetic Interference From Transceivers.

Electrostatic Discharge (ESD)

8 KV contact discharges and 15 KV air discharges applied in accordance with IEC EN61000-4-2 criterion.

Shock

In standard tests, the relay has withstood 2 g in each of three mutually perpendicular planes shock

without structural damage or degradation of performance.

Vibration

In standard tests, the relay has withstood 2 g in each of three mutually perpendicular planes, swept over

the range of 10 to 500 Hz for a total of six sweeps, 15 minutes each sweep, without structural damage or

degradation of performance.