Basler Electric BE1-851 User Manual

Page 145

Advertising
background image

Table 7-2. Logic Variable Names and Descriptions for Sensing Input Type G Relays

Variable

Name

Description

Variable

Name

Description

Inputs and Outputs

Time Overcurrent

IN1 – IN4

Inputs 1 through 4 Status

51PT

51 Phase Tripped

VOA

Relay Trouble Alarm Output Status

51PPU

51 Phase Picked Up

VO1 – VO5

Virtual Outputs 1 through 5 (hardware outputs)

51NT

51 Neutral Tripped

VO6 – VO15

Virtual Outputs 6 through 15

51NPU

51 Neutral Picked Up

Controls

151NT

51 Neutral Tripped

RSTKEY

HMI Target Reset Key

151NPU

151 Neutral Picked Up

101T

Virtual Breaker Control Switch Tripped

Instantaneous Overcurrent

101C

Virtual Breaker Control Switch Closed

50TPT

50T Phase Tripped

101SC

Virtual Breaker Control Switch Slip Contact

50TPPU

50T Phase Picked Up

62

62 Timer Output

50TNT

50T Neutral Tripped

162

162 Timer Output

50TNPU

50T Neutral Picked Up

262

262 Timer Output (Available when style

option 1 is V or W.)

150TPT

150T Phase Tripped

362

362 Timer Output (Available when style

option 1 is V or W.)

150TPPU

150T Phase Picked Up

43

Virtual Switch 43 Output

150TNT

150T Neutral Tripped

143

Virtual Switch 143 Output

150TNPU

150T Neutral Picked Up

243

Virtual Switch 243 Output (Not available

when style option 1 is V or W.)

250TNT

250T Neutral Tripped

343

Virtual Switch 343 Output (Not available

when style option 1 is V or W.)

250TNPU

250T Neutral Picked Up

SG0

Setting Group 0 Active (default)

350TNT

350T Neutral Tripped

SG1

Setting Group 1 Active

350TNPU

350T Neutral Picked Up

SG2

Setting Group 2 Active

SG3

Setting Group 3 Active

Alarms and Monitor

ALMLGC

Logic Alarm

ALMMAJ

Major Alarm

ALMMIN

Minor Alarm

OUT1MON

Output 1 Monitor (circuit continuity)

Reclosing

79C

79 Close Signal

79RNG

79 Running/Block Tap Changer

79LO

79 Lock Out

79F

79 Reclose Fail

79SCB

79 Sequence Control Block

Breaker Failure

BFT

Breaker Failure Tripped

BFPU

Breaker Failure Picked Up





9289900990 Rev R

BE1-851 BESTlogic™ Programmable Logic

7-5

Advertising