Basler Electric BE1-851 User Manual

Page 205

Advertising
background image

Output

Purpose

Description

Label

State Labels

True

False

VO5

(OUT5)

Feeder breaker trip.

Trip feeder breaker via auxiliary

relay (94) for time (51) and

instantaneous (50T with 2-4

cycles delay) when in feeder

relay backup mode and not in

test mode.

BKR_FAIL

TRIP

NORMAL

BESTlogic Expression: VO5=VO11*SG1*/VO15

VO6

N/A

N/A

VO6

TRUE

FALSE

BESTlogic Expression: VO6=0

VO7

N/A

N/A

VO7

TRUE

FALSE

BESTlogic Expression: VO7=0

VO8

Time overcurrent trip.

TRUE if any of the time

overcurrent elements trip.

51_TRIP

TRIP

NORMAL

BESTlogic Expression: VO8=51PT+51NT+51QT

VO9

Instantaneous overcurrent

trip.

TRUE if any of the instantaneous

overcurrent elements trip.

50_TRIP

TRIP

NORMAL

BESTlogic Expression: VO9=50TPT+50TNT+50TQT

VO10

N/A

N/A

VO10

TRUE

FALSE

BESTlogic Expression: VO10=0

VO11

Protective Trip

Expression.

TRUE when any 50 or 51

element times out.

PROT_TRIP

TRIP

NORMAL

BESTlogic Expression: VO11=50TPT+50TNT+50TQT+51PT+51NT+51QT

VO12

Protection Pickup Up

Expression.

TRUE when any 50 or 51

element picks up.

PROT_PU

PU

NORMAL

BESTlogic Expression: VO12=50TPPU+50TNPU+50TQPU+51PPU+51NPU+51QPU

VO13

Relay is in feeder backup

mode.

TRUE if in setting group 1.

FEEDER_BU BACKUP NORMAL

BESTlogic Expression: VO13=SG1

VO14

N/A

N/A

VO14

TRUE

FALSE

BESTlogic Expression: VO14=0

VO15

The relay is in test mode,

breaker failure is

disabled, and reclosing is

disabled.

TRUE if IN4 is de-energized or if

Virtual Switch 343 is closed.

TEST_MODE

TEST

NORMAL

BESTlogic Expression: VO15=/IN4+343







9289900990 Rev R

BE1-851 Application

8-49