Table 8-14. feeder_3 function block logic -29 – Basler Electric BE1-851 User Manual

Page 185

Advertising
background image

Table 8-14. Feeder_3 Function Block Logic

Function

Purpose

BESTlogic

Expression

Mode

Setting

50TP

Used for instantaneous phase overcurrent protection.

Block when recloser sequence controlled blocking

output is TRUE.

79SCB

1 (enabled)

50TN

Used for instantaneous neutral overcurrent protection.

Block when recloser sequence controlled blocking

output is TRUE or when disabled by IN3 or Virtual

Switch 243.

79SCB+/IN3+243 1 (enabled)

50TQ

Used for instantaneous negative-sequence

overcurrent protection. Block when recloser sequence

controlled blocking output is TRUE or when disabled

by /IN3 or Virtual Switch 243.

79SCB+/IN3+243 1 (enabled)

150TP

Used for instantaneous phase overcurrent protection.

0

1 (enabled)

150TN

Used for instantaneous neutral overcurrent protection.

0

1 (enabled)

150TQ

Used for instantaneous negative-sequence

overcurrent protection.

0

1 (enabled)

51P

Used for timed phase overcurrent protection.

0

1 (enabled)

51N

Used for timed neutral overcurrent protection. Block

when disabled by IN3 or Virtual Switch 243.

/IN3+243

1 (enabled)

51Q

Used for timed negative-sequence overcurrent

protection. Block when disabled by IN3 or Virtual

Switch 243.

/IN3+243

1 (enabled)

62

N/A

0

0 (disabled)

162

N/A

0

0 (disabled)

79

RI Logic: Strapped high.

/0

1 (Power Up

to Lockout)

STATUS Logic: Breaker closed when IN1 is de-

energized.

/IN1

WAIT Logic: Stop recloser timing when timing for a

fault trip. TRUE when protection picked up expression

is TRUE.

VO12

BLK/DTL Logic: Drive recloser to lockout when

recloser drive to lockout expression is TRUE or when

relay is in test mode.

VO9+/IN4+343

BF

Initiate breaker failure when breaker failure initiate

expression is TRUE.

VO10

1 (enabled)

Block breaker failure protection when relay is in test

mode.

/IN4+343

GROUP

No manual selection logic is used.

0

1 (Discrete

Inputs)

No manual selection logic is used.

0

No manual selection logic is used.

0

No manual selection logic is used.

0

Disable automatic selection when Virtual Switch 43 is

in the manual position.

/43

9289900990 Rev R

BE1-851 Application

8-29

Advertising