Retrieving output logic override status – Basler Electric BE1-851 User Manual

Page 52

Advertising
background image

2. Test all outputs by pulsing momentarily.

>CS-OUT=P

OUT=P SELECTED

>CO-OUT=P

OUT=P EXECUTED

3. Disable the trip output (OUT1) by holding it at logic 0.

>CS-OUT1=0

OUT1=0 SELECTED

>CO-OUT1=0

OUT1=0 EXECUTED

4. Return OUT1 to logic control.

>CS-OUT1=L

OUT1=L SELECTED

>CO-OUT1=0

OUT1=L EXECUTED

5. Disable the output control feature.

>CS-OUT=DIS

OUT=DIS SELECTED

>CO-OUT=DIS

OUT=DIS EXECUTED

>E (exit)

Save Changes (Y/N/C)?

>Y (yes)

Retrieving Output Logic Override Status

The status of the output contact logic override control can be viewed at HMI Screen 1.5.3. HMI Screen

2.4.1 is used for output control but can also display the current status. Output logic status can also be

viewed using the RG-STAT (report general-status) command. An L indicates that the state of the output is

controlled by logic. A 0 or 1 indicates that the logic has been overridden and the contact is held open (0)

or closed (1) state. A P indicates that the contact is being pulsed and will return to logic control

automatically. See Section 6, Reporting and Alarms, General Status Reporting, for more information.



3-10

BE1-851 Input and Output Functions

9289900990 Rev R