Basler Electric BE1-851 User Manual

Page 252

Advertising
background image

RB Command

Purpose:

Read breaker status

Syntax:

RB

Example:

RB

Reference:

Section 6, Reporting and Alarms, Breaker Monitoring

RB-DUTY Command

Purpose:

Read/Set breaker contact Duty Log

Syntax:

RB-DUTY[{phase}[={%duty}]] where %duty is % of dmax set with SB-DUTY

Example:

RB-DUTYA or RB-DUTYB=50

Reference:

Section 6, Reporting and Alarms, Breaker Monitoring

RB-OPCNTR Command

Purpose:

Read/Set Breaker Operation Counter

Syntax:

RB-OPCNTR[={#operations}]

Example:

RB-OPCNTR=32 or RB-OPCNTR=652

Reference:

Section 6, Reporting and Alarms, Breaker Monitoring

RD Command

Purpose:

Report all demand data

Syntax:

RD

Example:

RD

Reference:

Section 6, Reporting and Alarms, Demand Functions

RD-PI Command

Purpose:

Read/Reset peak demand current (I)

Syntax:

RD-PI[{p}[=0]] where p=A/B/C/N/Q

Example:

RD-PI or RD-PIA or RD-PIN or RD-PI=0

Reference:

Section 6, Reporting and Alarms, Demand Functions

RD-TI Command

Purpose:

Report today's demand current (I)

Syntax:

RD-TI[{p}] where p=A/B/C/N/Q

Example:

RD-TI or RD-TIA or RD-TIN

Reference:

Section 6, Reporting and Alarms, Demand Functions

RD-YI Command

Purpose:

Report yesterday's demand current (I)

Syntax:

RD-YI[{p}] where p=A/B/C/N/Q

Example:

RD-YI or RD-YIA or RD-YIN

Reference:

Section 6, Reporting and Alarms, Demand Functions

RF Command

Purpose:

Read/Reset Fault Report Data

Syntax:

RF[-n/NEW][=0]

Example:

RF (displays a directory of all fault reports in memory)

RF-23 (view summary report for fault record 23)

RF-NEW (view summary report for newest fault record since RF=0 reset)

RF=TRIG (Manually Trigger a fault record)

RF=0 (reset NEW fault counter)

Reference:

Section 6, Reporting and Alarms, Fault Reporting

11-10

BE1-851 ASCII Command Interface