50BF Breaker Failure Protection
Pickup

Setting Range ................................................................. Fixed at 0.5 A for 5 A unit, 0.1 A for 1 A unit

Accuracy ......................................................................... ±10%

Time Delay

Setting Range ................................................................. 50 to 999 ms

Accuracy ......................................................................... ±5% or ±¼ cycle, whichever is greater

Reset Time ..................................................................... Within 1¼ cycles of the current being removed

51 Time Overcurrent Protection
Pickup

5 Ampere CT Setting Range .......................................... 0.5 to 16 A

1 Ampere CT Setting Range .......................................... 0.1 to 3.2 A

Dropout/Pickup Ratio:

95%

Accuracy (51P, 51N)

5 Ampere CT .................................................................. ±2% or ±50 mA, whichever is greater

1 Ampere CT .................................................................. ±2% or ±10 mA, whichever is greater

Accuracy (51Q)

5 Ampere CT .................................................................. ±3% or ±75 mA, whichever is greater

1 Ampere CT .................................................................. ±3% or ±15 mA, whichever is greater

Time Current Characteristic Curves

Timing Accuracy (All 51 Functions) ................................ Within ±5% or ±1½ cycles, whichever is greater,

for time dial settings greater than 0.1 and

multiples of 2 to 40 times the pickup setting but

not over 150 A for 5 A CT units or 30 A for 1 A CT

units.
See Appendix A, Time Overcurrent Characteristic

Curves, for information on available timing curves.

62 Logic Timers

Modes ............................................................................. Pickup/Dropout, Integrating, Retriggerable, Non-

Retriggerable, Oscillator, and Latch

Setting Range ................................................................. 0 to 9,999 s

Accuracy ......................................................................... ±5% or ±¾ cycle, whichever is greater

262 and 362 are available when style option 1 is V or W.

79 Recloser Protection
Reclose (791, 792, 793, 794), Reset (79R), Max Cycle (79M), Reclose Fail (79F)

Setting Range ................................................................. 100 ms to 600 s

Accuracy ......................................................................... ±5% or +1.75, −0 cycles, whichever is greater

Automatic Setting Group Characteristics

Number of Setting Groups:

4

Switch Level

Range ............................................................................. 0-150% of the setting group 0, 51 phase pickup

setting (SO-51P)

Accuracy ......................................................................... ±2% or ±50 mA (5 A), ±2% or ±10 mA (1 A)

Switch Timer

Range ............................................................................. Range 0-150% of the setting group 0, 51 phase

pickup setting (SO-51P)

Accuracy ......................................................................... ±5% or ±2 s, whichever is greater