Operational specifications, Metered current values and accuracy, Calculated values and accuracy – Basler Electric BE1-851 User Manual

Page 23: Demand, 50t instantaneous overcurrent protection, Pickup, Accuracy (50tp, 50tn), Accuracy (50tq), Time delay, Accuracy

Advertising
background image

Operational Specifications

BE1-851 relays have the following features and capabilities.

Metered Current Values and Accuracy

Current Range ................................................................ 0.1 to 1.5 nominal

Accuracy (Phase and Neutral) ........................................ ±1% of reading, ±1 least significant digit at 25°C

Accuracy (Negative-Sequence) ...................................... ±1.5% of reading, ±1 least significant digit at 25°C

Temperature Dependence .............................................. ≤ ±0.02% per °C

Calculated Values and Accuracy
Demand

Range ............................................................................. 0.1 to 1.5 nominal

Type ................................................................................ Exponential

Accuracy ......................................................................... ±1% of reading ±1 digit at 25°C

Interval ............................................................................ 1 to 60 minutes

50T Instantaneous Overcurrent Protection
Pickup

5 Ampere CT Setting Range .......................................... 0.5 to 150 A

1 Ampere CT Setting Range .......................................... 0.1 to 30 A

Dropout/Pickup Ratio ...................................................... 95%

Accuracy (50TP, 50TN)

5 Ampere CT .................................................................. ±2% or ±50 mA, whichever is greater

1 Ampere CT .................................................................. ±2% or ±10 mA, whichever is greater

Accuracy (50TQ)

5 Ampere CT .................................................................. ±3% or ±75 mA, whichever is greater

1 Ampere CT .................................................................. ±3% or ±15 mA, whichever is greater

Time Delay

Setting Range ................................................................. 0 to 60 s

Accuracy

50TP, 50TN .................................................................... ±0.5% or ±¼ cycle, whichever is greater, Plus trip

time for instantaneous response (0.0 setting)∗

50TQ ............................................................................... ±0.5% or ±1 cycle, whichever is greater, Plus trip

time for instantaneous response (0.0 setting)∗

Trip Time for 0.0 Delay Setting

50TP, 50TN .............................................................. 1¼ cycles maximum for currents ≥ 5 times the

pickup setting. Three cycles maximum for a

current of 1.5 times pickup. Four maximum for a

current of 1.05 times the pickup setting.

50TQ ........................................................................ 2¼ cycles maximum for currents 5 times the

pickup setting. Three maximum for a current of

1.5 times pickup. Five cycles maximum for a

current of 1.05 times the pickup setting.

9289900990 Rev R

BE1-851 General Information

1-7