51 pickups and dropouts, 51 pickups and dropouts -5, Table 13-8. pickup settings -5 – Basler Electric BE1-851 User Manual

Page 293: Table 13-9. pickup ranges -5

Advertising
background image

Step 7:

After pickup occurs, ramp the current down slowly until OUT1 opens. Dropout should occur

at 90% ±2% of the pickup current magnitude.

Step 8:

Transmit the appropriate command in Table 13-8 to reprogram the pickup setting.

Table 13-8. Pickup Settings

Style Number

Commands

Phase

Neutral

x1xxxxx

S0-50TP=5.0A,0m

S0-50TN=5.0A,0m

x3xxxxx

S0-50TP=25.0A,0m

S0-50TN=5.0A,0m

x5xxxxx

S0-50TP=25.0A,0m

S0-50TN=25.0A,0m


Step 9:

Slowly ramp up the current applied at the relay Phase A input until OUT1 closes. Verify that

pickup occurred within the acceptable range listed in Table 13-9.

Table 13-9. Pickup Ranges

Style

Number

Phase

Neutral

Low Limit

High Limit

Low Limit

High Limit

x1xxxxx

4.9 amps

5.1 amps

4.9 amps

5.1 amps

x3xxxxx

24.5 amps

25.5 amps

4.9 amps

5.1 amps

x5xxxxx

24.5 amps

25.5 amps

24.5 amps

25.5 amps


Step 10:

After pickup occurs, ramp the current down slowly until OUT1 opens. Dropout should occur

at 90% ±2% of the pickup current magnitude.

Step 11:

Repeat Steps 2 through 10 for the Phase B current input.

Step 12:

Repeat Steps 2 through 10 for the Phase C current input.

Step 13:

Repeat Steps 2 through 10 for the Neutral current input.

51 Pickups and Dropouts

Step 1:

Transmit the following scheme to the relay:

ACCESS=851

SL-N=NONE

YES

SL-N=PU51

SL-51=1,0

SL-VO1=51PT+51NT

EXIT;Y

Step 2:

Transmit the appropriate command in Table 13-10 to program the pickup setting.

9289900990 Rev R

BE1-851 Testing and Maintenance