Table 6-7. breaker alarms settings -15 – Basler Electric BE1-851 User Manual

Page 117

Advertising
background image

Using the pull-down menus and buttons, make the application appropriate settings to the Breaker Alarms

function. Table 6-7 summarizes the Breaker Alarms settings.

Table 6-7. Breaker Alarms Settings

Setting

Range/Purpose

Default

Mode

0 = Disabled, 1 = Duty breaker alarm function enabled and set for

percent duty, 2 = Operations breaker alarm function enabled and set for

operations counting, 3 = Clearing Time breaker alarm function enabled

and set for breaker operate time.

0

Alarm Threshold

(in mode 1)

0 to 100%; Increment=0.01; Measured in % of Dmax which is

programmed using the SB-DUTY command. The breaker to be

monitored (CT1 or CT2) is also programmed using the SB-DUTY

command.

0

Alarm Threshold

(in mode 2)

0 to 99999, Increment=1; Number of operations counter value which

when reached would cause an alarm.

0

Alarm Threshold

(in mode 3)

Ranges are 20 to 1,000 milliseconds and 2 to 60 cycles. Setting is

reported in milliseconds if less than 1 second but may be entered in

milliseconds (m), seconds (s), or cycles (c).

0


Example 1.

Make the following setting to the Breaker Alarms function. Refer to Figure 6-7

Breaker Alarms Point 1, Mode:

Operations

Breaker Alarms Point 1, Threshold:

20

Breaker Alarms Point 2, Mode:

Duty

Breaker Alarms Point 2, Threshold:

50

Breaker Alarms Point 3, Mode:

Clearing Time

Breaker Alarms Point 3, Threshold:

20

9289900990 Rev R

BE1-851 Reporting and Alarms

6-15