Time overcurrent characteristic curves – Basler Electric BE1-851 User Manual

Page 332

Advertising
background image

Table A-1. 51P, 51N, and 51Q Time Characteristic Curve Constants

Curve

Selection

Curve Name

Trip Characteristic Constants

Reset

A

B

C

N

K

R

S1

Short Inverse

0.2663 0.03393

1

1.2969

0.028

0.5

S2

Short Inverse

0.0286

0.0208

1

0.9844

0.028

0.094

L1

Long Inverse

5.6143 2.18592

1

1

0.028

15.75

L2

Long Inverse

2.3955

0

1

0.3125

0.028

7.8001

D

Definite Time

0.4797 0.21359

1

1.5625

0.028

0.875

M

Moderately Inverse

0.3022

0.1284

1

0.5

0.028

1.75

I1

Inverse Time

8.9341 0.17966

1

2.0938

0.028

9

I2

Inverse Time

0.2747 0.10426

1

0.4375

0.028

0.8868

V1

Very Inverse

5.4678 0.10814

1

2.0469

0.028

5.5

V2

Very Inverse

4.4309

0.0991

1

1.9531

0.028

5.8231

E1

Extremely Inverse

7.7624 0.02758

1

2.0938

0.028

7.75

E2

Extremely Inverse

4.9883

0.0129

1

2.0469

0.028

4.7742

A

Standard Inverse

0.01414

0

1

0.02

0.028

2

B

Very Inverse (I

2

t)

1.4636

0

1

1.0469

0.028

3.25

C

Extremely Inverse (I

2

t)

8.2506

0

1

2.0469

0.028

8

G

Long Time Inverse (I

2

t)

12.1212

0

1

1

0.028

29

F

Fixed Time ∗

0

1

0

0

0.028

1

P

Programmable ‡

0 to 600 0 to 25

0 to 1

0.5 to 2.5

0.028

0 to 30


Curve F has a fixed delay of one second times the Time Dial setting.

† For integrated reset, append

R to the curve name. For example, curve S1 has instantaneous reset.

Curve

S1R has integrated reset.

The programmable curve allows for four significant digits after the decimal place for every variable.

Time Overcurrent Characteristic Curves

Figures A-1 through A-16 illustrate the characteristic curves of the BE1-851 relay. Table A-2 cross-

references each curve to existing electromechanical relay characteristics. Equivalent time dial settings

were calculated at a value of five times pickup.

A-2

BE1-851 Time Overcurrent Characteristic Curves

9289900990 Rev R