Basler Electric BE1-851 User Manual

Page 215

Advertising
background image

BACKUP Logic Settings and Equations for Sensing Input Type H Relays

SL-N=BACKUP

SL-50TP = 1,0

SL-50TN = 1,0

SL-50TQ = 1,0

SL-150TP = 1,0

SL-150TN = 1,0

SL-150TQ = 1,0

SL-51P = 1,0

SL-51N = 1,0

SL-51Q = 1,0

SL-62=0,0,0

SL-162=0,0,0

SL-79 = 0,0,0,0,0

SL-BF = 1,VO10,VO15

SL-GROUP = 2,/IN2,0,0,0,0

SL-43 = 0

SL-143 = 0

SL-243 = 0

SL-343 = 2

SL-101 = 1

SL-VOA = ALMMAJ

SL-VO1 = 101T+VO8+BFPU+VO11*VO15

SL-VO2 = 101C

SL-VO3 = /IN2

SL-VO4 = VO9*/VO15

SL-VO5 = BFT

SL-VO6 = 0

SL-VO7 = 0

SL-VO8 = 51PT+51NT+51QT

SL-VO9 = 50TPT+50TNT+50TQT

SL-VO10 = VO11+IN3*150TPPU+IN3*150TNPU+IN3*150TQPU

SL-VO11 = 50TPT+50TNT+50TQT+51PT+51NT+51QT

SL-VO12 = 50TPPU+50TNPU+50TQPU+51PPU+51NPU+51QPU

SL-VO13 = 0

SL-VO14 = 0

SL-VO15 = /IN4+343

BACKUP Logic Settings and Equations for Sensing Input Type G Relays

SL-N=BACKUP

SL-50TP = 1,0

SL-50TN = 1,0

SL-150TP = 1,0

SL-150TN = 1,0

SL-250TN = 0,0

SL-350TN = 0,0

SL-51P = 1,0

SL-51N = 1,0

SL-151N = 0,0

SL-62 = 0,0,0

SL-162 = 0,0,0

SL-79 = 0,0,0,0,0

SL-BF = 1,VO10,VO15

SL-GROUP = 2,/IN2,0,0,0,0

SL-43 = 0