group three return timer begins timing. Current varies but stays below 75 percent for 5 minutes and at

time = 75, setting group two becomes active and the setting change output pulses. After 20 minutes,

setting group zero becomes active and the setting change output pulses.

Figure 4-6. Automatic Operation Based on Load Change


This function can also be used to automatically change the active setting group for cold load pickup

conditions. If the switch to threshold for a group is set to 0%, the function will switch to that group when

there is no current flow for the time delay period indicating that the breaker is open or the circuit source is

out of service. The threshold for this is 10% nominal rating of the relay current input.
Figure 4-8 shows how the active setting group follows the load current and time delay settings. Figure 4-7

illustrates the operating settings used in the diagram shown in Figure 4-8. Note that the AUTO input must

be at a TRUE (1) logic state for the automatic logic to operate. When the breaker opens, the load current

falls to zero, time = 15 minutes. After 10 minutes, setting group one becomes active and the setting group

change output pulses TRUE. When the breaker is closed, time = 40 minutes, load current increases to

approximately 90 percent of pickup. As the load current decreases to 50 percent of pickup, the setting

group one return timer begins timing. After ten minutes, setting group one output goes FALSE, the setting

group returns to setting group zero, and the setting group change output pulses TRUE.
When the switch to criteria is met for more than one setting group at a time, the function will use the

numerically higher of the enabled setting groups. If the switch to time delay setting is set to 0 for a setting

group, automatic control for that group is disabled. If the return time delay setting is set to 0 for a setting

group, automatic return for that group is disabled and the relay will remain in that setting group until

returned manually by logic override control.




9289900990 Rev R