Figure 4-40. BESTlogic Function Element Screen, 43

At the top center of the BESTlogic Function Element screen is a pull-down menu labeled Logic. This

menu allows viewing of the BESTlogic settings for each preprogrammed logic scheme. User must be

selected on this menu in order to allow changes to the mode and inputs of the element.
Enable the Virtual Switch element by selecting its mode of operation from the Mode pull-down menu.

Select Done when the settings have been completely edited.
Table 4-18 summarizes the BESTlogic settings for Virtual Selector Switches.

Table 4-18. BESTlogic Settings for Virtual Selector Switches

Function

Range/Purpose

Default

Mode

0 = Disabled
1 = On/Off/Pulse

2 = On/Off
3 = Off/Momentary On

0

Example 1. Make the following settings to the 43 Virtual Switch element. See Figure 4-40.

Logic:

User

Mode:

Off/Momentary On

Select Before Operate Control of Virtual Selector Switches

The state of each virtual selector switch can be controlled at the human-machine interface (HMI) through

Screens 2.1.1 through 2.1.4. Control is also possible through the ASCII command interface by using the

select-before-operate command’s CS-x43 (control select-virtual switch) and CO-x43 (operate select-

virtual switch). This is not possible through BESTCOMS. A state change takes place immediately without

having to execute an EXIT – SAVE settings command.
The virtual switch control commands require the use of select-before-operate logic. First, the command

must be selected using the CS-x43 command. After the select command is entered, there is a 30 second

window during which the CO-x43 control command will be accepted. The control selected and the

operation selected must match exactly or the operate command will be blocked. If the operate command

is blocked an error message is output.