Basler Electric BE1-851 User Manual

Page 169

Advertising
background image

Output

Purpose

Description

Label

State Labels

True

False

VO8

Time overcurrent trip.

TRUE if any of the time

overcurrent elements trip.

51_TRIP

TRIP

NORMAL

BESTlogic Expression: VO8=51PT+51NT+51QT

VO9

Instantaneous

overcurrent trip.

TRUE if any of the

instantaneous overcurrent

elements trip.

50_TRIP

TRIP

NORMAL

BESTlogic Expression: VO9=50TPT+50TNT+50TQT

VO10

Breaker failure initiate

expression.

Initiate breaker failure timing

when protective trip expression

is TRUE.

BFI

INI

NORMAL

BESTlogic Expression: VO10=VO11

VO11

Protective Trip

Expression.

TRUE when any 50 or 51

element times out.

PROT_TRIP

TRIP

NORMAL

BESTlogic Expression: VO11=50TPT+50TNT+50TQT+51PT+51NT+51QT

VO12

Protection Picked Up

Expression.

TRUE when any 50 or 51

element picks up.

PROT_PU

PU

NORMAL

BESTlogic Expression: VO12=50TPPU+50TNPU+50TQPU+51PPU+51NPU+51QPU

VO13

N/A

N/A

VO13

TRUE

FALSE

BESTlogic Expression: VO13=0

VO14

N/A

N/A

VO14

TRUE

FALSE

BESTlogic Expression: VO14=0

VO15

The relay is in test mode,

breaker failure is

disabled, and all trips are

rerouted to OUT1.

TRUE if IN4 is de-energized.

TEST_MODE

TEST

NORMAL

BESTlogic Expression: VO15=/IN4

9289900990 Rev R

BE1-851 Application

8-13