Basler Electric BE1-851 User Manual

Page 253

Advertising
background image

RG Command

Purpose:

Report General Information

Syntax:

RG

Example:

RG

Reference:

Section 6, Reporting and Alarms, Clock

RG-DATE Command

Purpose:

Report/Set Date

Syntax:

RG-DATE[={M/D/Y}] or RG-DATE[={D-M-Y}]

Example:

RG-DATE=12/31/96 or RG-DATE=31-12-96 (Format set by SG-CLK Command)

Reference:

Section 6, Reporting and Alarms, Clock

RG-DST Command

Purpose:

Report start and stop times and dates for Daylight Saving Time referenced to local time.

Syntax:

RG-DST

Example:

RG-DST

Reference: Section 6, Reporting and Alarms, Clock

RG-STAT Command

Purpose:

Report relay status

Syntax:

RG-STAT

Example:

RG-STAT

Reference:

Section 6, Reporting and Alarms, General Status Reporting

RG-TARG Command

Purpose:

Report/Reset Target status

Syntax:

RG-TARG

Example:

RG-TARG or RG-TARG=0

Reference:

Section 6, Reporting and Alarms, Fault Reporting

RG-TIME Command

Purpose:

Report/Set Time

Syntax:

RG-TIME[=hr:mn:sc] or RG-TIME[=hr:mn{f}sc]]

Example:

RG-TIME=13:25:00 or RG-TIME=1:25P00 (Format(f) set by SG-CLK Command)

Reference:

Section 6, Reporting and Alarms, Clock

RG-VER Command

Purpose:

Read Model #, Style #, Program Version, Serial #

Syntax:

RG-VER

Example:

RG-VER

Reference:

Section 6, Reporting and Alarms, Hardware and Software Version Reporting

RO Command

Purpose:

Read Oscillographic COMTRADE .DAT/.CFG/.HDR Fault Report

Syntax:

RO-nA/B[#].CFG/DAT/HDR where n=report number,A=ASCII/B=BINARY,#=OSC 1/2

Example:

RO-3A1.CFG or RO-3A1.DAT or RO-5B2.CFG or RO-5B2.DAT or RO-5A.HDR

Reference:

Section 6, Reporting and Alarms, Fault Reporting






9289900990 Rev R

BE1-851 ASCII Command Interface

11-11

Advertising